Doc: I456GB06_16.docx 29/06/2016
p. 16 / 20
Commands menu
The commands menu is used to perform occasional operations, like resetting measurements, counters, alarms, etc.
If the advanced access password was entered, the commands menu can also be used to perform automatic operations useful for configuring the instrument.
The following table shows the functions which are available with the commands menu divided according to the required access level.
CODE
CONTROL
ACCESS LEVEL
DESCRIPTION
C01
MAINTENANCE RESET
ADVANCED
Resets the maintenance interval and resets the alarm
C02
THERMAL STATUS RESET
ADVANCED
Sets the thermal status to 0%
C03
START COUNTER RESET
ADVANCED
Resets the number of startings counter
C04
HOUR METER RESET
ADVANCED
Resets the motor's hour meter
C05
ENERGY METER RESET
ADVANCED
Resets the energy counters
C06
LIMITS RESET
ADVANCED
Resets LIM variables with memory
C11
REPEAT AUTO SET
USER
Repeats the AUTOSET wizard
C12
SETUP TO DEFAULT
USER
Restores the factory default settings
C13
BACKUP SETUP
ADVANCED
Saves a copy of the setup parameters
C14
RESTORE SETUP
ADVANCED
Restores a copy of the setup parameters
C15
TEST LOW POWER MOTOR
ADVANCED
Test with low power motor – Ignores current-related alarms for a bench test
with low power motors
Installation
Recommendations
Switch off power to the soft starter every time you need to work on the electrical or mechanical equipment of the system or machine.
A disconnecting device, such as switch disconnector, line contactor, etc. must always be included to cut off the power supply.
Never use the starter to drive motor power transformers.
Do not install the starter in areas containing flammable gas or explosives.
Do not place the soft starter close to sources of heat.
Do not use an insulating enclosure since they are poor heat conductors.
You can protect the starter's SCR's properly against short circuit only by using ultra-rapid fuses. To select the fuses, refer to the tables on the last pages of this manual. Note that when
the bypass relay switch is closed (i.e. motor running), the SCR's are protected against short circuit, overload and overvoltage.
Power factor correction
If power factor correction capacitors are to be used, they must be installed upstream of the soft starter, with a contactor and protection fuses. They must be engaged once starting has
terminated, and disengaged before stopping. The contactor can be controlled with a relay output programmed to “RUN”.
t <45°
t <45°
t <45°
100mm
50mm
50mm
100mm