Doc: I456GB06_16.docx
29/06/2016
p. 4 / 20
Navigating the display pages
The
▲
and
▼
buttons allow the measurement display pages to be scrolled one at a time. The current page is shown in text.
Some of the values may not display, depending on how the starter has been programmed.
VALUE
DISPLAY
UOM
Instantaneous current (highest of three phases)
CURRENT
A
Instantaneous current as % of nominal motor current
CURRENT
A %
Phase L1 current (displayed if enabled with parameter P02.07)
CURR L1
A
Phase L2 current (displayed if enabled with parameter P02.07)
CURR L2
A
Phase L3 current (displayed if enabled with parameter P02.07)
CURR L3
A
Motor torque as % of maximum nominal torque
TORQUE
%
Phase-to-phase line voltage
VOLTAGE
V
Total active power
POWER kW
kW
Total PF
PF TOT.
Motor thermal status (note: protection trips at > 140%)
THERM. ST.
%
Starter thyristor temperature
INT. TEMP
°
Energy in kWh
ENER. kWh
kWh alternating with value
Motor hour meter
HOURS
H alternating with value
Start counter
ST. COUNT
alternating with value
Input/output status (on side bars)
INP OUT
LIMx limit variable status
LIM
The user can specify to which value the display must return automatically after no buttons have been pressed for a given time.
The system can be programmed so that the view always remains in the position in which it was left.
For the set-up of these functions, see the
P02 – UTILITY
menu.
Operational status
During normal operation, if the user does not press the navigation keys to view values, the text bar indicates the starter's status.
The possible statuses are given in the following table, with their explanations:
STATUS
DISPLAY
DESCRIPTION
Line absent
NO POWER
No power to terminals L1-L2-L3.
Starter ready
READY
Power present, starter ready to run.
Start delay xx
DELAY XX
Delay applicable to the current start command. A countdown displays.
Start kick
KICK.STA
Kickstart in progress.
Acceleration ramp
ACC. RAMP
Motor acceleration ramp in progress.
Current limit
CURR. LIM.
Current limitation during acceleration ramp.
Torque limit
TRQ. LIM.
Torque limitation during acceleration ramp.
Run
RUN
End of acceleration ramp, full voltage to motor via SCR.
By-pass closed
BYPASS
End of acceleration ramp, full voltage to motor via bypass contactor.
Deceleration ramp
DEC. RAMP
Motor deceleration ramp in progress.
Protections disabled
INH. PROT.
Protections disabled by external command.
Freewheel
FREEWHEEL
External free-range stop command.
Preheating
PREHEAT
Motor winding preheating enabled.
Alarm
ALARM
One or more alarms present.
Remote keypad
All information available on the display can be viewed remotely on a keypad which installs on the front panel.
The remote keypad (code EXCRDU1) is of the standard 96x96mm format and features a graphic touch screen display. It has a 3m cable.
The remote keypad connects to the ADXL via the optional RS-485 interface on the EXC1042 minicard.
The maximum distance between the ADXL and the remote keypad is 1000m.
The keypad can connect to multiple ADXL's at once (up to 4 units), with all data displaying on a single operator panel.