Choosing the soft starter 
 

Code Starter 

rated 

current  Ie [A] 

Rated duty power IEC 

FLA [A] 

Rated duty power UL 

 

Motor power [kW] 

Motor power [Hp] 

 

P

e

@230 

VAC 

P

e

@400 

VAC 

P

e

@500 

VAC 

P

e

@208 

VAC 

P

e

@220-

240 VAC 

P

e

@380-

415 VAC 

P

e

@440-

480 VAC 

P

e

@550-

600 VAC 

ADXL 0030 600 

30 7.5 

15 

18.5 

28 

10 

10 

15 20 25 

ADXL 0045 600 

45 

11 22 30 

44 

10 

15 

25 30 40 

ADXL 0060 600 

60 

15 30 37 

60 

20 

20 

30 40 50 

ADXL 0075 600 

75 

22 37 45 

75 

25 

25 

40 50 60 

ADXL 0085 600 

85 

22 45 55 

83 

25 

30 

50 60 75 

ADXL 0115 600 

115  37 55 75 

114 

40 

40 

60 75 100 

ADXL 0135 600 

135  37 75 90 

130 

40 

50 

75 100 125 

ADXL 0162 600 

162 45 

90 

110 

156 

50 

60 

75 125 150 

ADXL 0190 600 

195 55 

110 

132 

192 

60 

60 

100 150 200 

ADXL 0250 600 

250 75 

132 

160 

248 

75 

100 

150 200 250 

ADXL 0320 600 

320 90 

160 

200 

320 

100 

125 

200 250 300 

 
Attention! The data in the table, relative to the rated operational power, were obtained in accordance with EN 60947-4-1: 2012-05, so the data in kW and HP are not linked 
together by the relation 1 Hp = kW * 1.36.  
 
 
Type 2 coordination 

 

TYPE 2 COORDINATION (IEC/EN 60947-4-2)  
 

Code 

Max fuse size 
Class aR [A] 

Fault current 
[kA] 

Max. voltage 
[VAC] 

FU1 Fuse 
Bussman 

British BS 88 
Bussman  

ADXL 0030 600 

80 5 

600 

FWP-80B 

80FE 

ADXL 0045 600 

125 5 

600 

FWP-125A 

120FEE 

ADXL 0060 600 

160 5 

600 

FWP-150A 

160FEE 

ADXL 0075 600 

250 10 

600 

FWP-175A 

180FEE 

ADXL 0085 600 

315 10 

600 

FWP-200A 

200FEE 

ADXL 0115 600 

400 10 

600 

FWP-250A 

250FM 

ADXL 0135 600 

450 10 

600 

FWP-300A 

315FM 

ADXL 0162 600 

500 10 

600 

FWP-500A 

500FMM 

ADXL 0190 600 

630 10 

600 

FWP-600A 

630FMM 

ADXL 0250 600 

700 18 

600 

FWP-700A 

700FMM 

ADXL 0320 600 

800 18 

600 

FWP-800A 

 

Technical characteristics

 

 

 

Auxiliary supply: terminals A1-A2 

 

Us rated voltage   

100 - 240V~ 

Operating range 

90 - 264V~ 

Frequency 

45 - 66 Hz 

Power draw/dissipation  

Size 1 

 
 

Size 2 

 

100V~ 110mA  5.5W 
240V~ 70mA    5.8W 

 

100V~ 120mA  6.8W 

240V~ 75mA    7W 

Immunity time for micro-interruptions 
 

40ms (110V~ ) 

160ms (220V~ ) 

Motor supply voltage L1 – L2 – L3 

Us rated voltage   

600V~ 

Operating range 

100-600V~ 

10% 

Frequency range 

45-65Hz 

Rated current and power 

(see table “

Choosing the soft starter

”, page 19) 

Digital inputs, terminals C - IN1, IN2

 

Input type 

Negative 

Applied voltage at contact 

5V= 

Input current 

10mA 

Low input signal  

0,8V 

High input signal 

3,2V 

Input signal delay 

50ms 

PTC input, terminals C - IN3 

 

Compatible types of PTC sensor 

Conforming with DIN 44081 

Total PTC sensor resistance 

 1,5 k

 a 25°C 

Trip resistance 

 2,9 k

 

Reset resistance 

 1,6 k

 

Fan power, terminals FAN + / - 

 

Fan voltage 

12V= supplied by starter 

Fan type 

Use exclusively accessory code EXP8004 

Output, terminals 11-12-14 

Output arrangement:  

1 NO/NC switching contact 

Summary of Contents for ADXL 0030 600

Page 1: ... or solvents Contents Page Description 2 Front button functions 2 Front LEDs 2 Display indications 2 AUTOSET guided configuration 3 Navigating the display pages 4 Operational status 4 Remote keypad 4 Startup methods 5 Protections 5 Motor thermal protection 6 Motor thermal protection via PTC 6 Starter thermal protection 6 Main menu 7 Password protected access 7 Inputs outputs internal variables 7 L...

Page 2: ...lay indication and alarm pre alarm thresholds Advanced self diagnostics NFC interface for programming with smartdevice Front mounted optical interface for programming and maintenance Isolated RS485 interface optional mounted in a dedicated slot with Modbus protocol Alarms with language specific messages and user programmable properties Compatible with the SAM1 App NFC App Synergy supervision softw...

Page 3: ...ion in sequence STEP INFORMATION DEFAULT RANGE 1 Display language ENG ENG ITA FRA ESP POR DEU 2 Nominal motor current 100 ADXL rating Example for ADXL0030600 30 0A 50 100 ADXL rating Example for ADXL0030600 15 0 30 0A 3 Type of starter application General purpose General purpose GP Centrifugal pump Fire fighting pump Belt conveyor Fan Mixer 4 Starter duty level Normal Light e g low inertia no load...

Page 4: ... does not press the navigation keys to view values the text bar indicates the starter s status The possible statuses are given in the following table with their explanations STATUS DISPLAY DESCRIPTION Line absent NO POWER No power to terminals L1 L2 L3 Starter ready READY Power present starter ready to run Start delay xx DELAY XX Delay applicable to the current start command A countdown displays S...

Page 5: ...ing a less gradual acceleration than the torque ramp Together with these two starting methods there is the maximum starting current limitation function o Current limit P01 02 If the current delivered by the highest of the three phases reaches or exceeds the set limit the ADXL reduces its voltage on the motor so as to remain below the maximum limit setting P01 02 This behaviour has priority over bo...

Page 6: ...maximum value which is 140 and trips alarm A14 Motor thermal protection The trip time is shown in the tables given below as a function of the overload current The curves for the various graphs refer to the curve selected with parameters P04 02 and P04 03 The cold trip curves indicate the trip time starting from thermal status 0 while the hot trip curves start from thermal status 100 With the motor...

Page 7: ...mmunication ports 1 Like the inputs outputs there are internal variables bit which may be associated to the outputs or combined For example limit thresholds can be applied to the measurements performed by the system voltage current etc In this case the internal variable named LIMx will be activated when the measurement is beyond the limits defined by the user by means of the respective setting men...

Page 8: ... the text of the message which must appear on the display when the condition occurs 3 the properties of the alarm like for the standard alarms i e so as to interact with the genset control For example going beyond a threshold may be a condition which generates the alarm In this case the source must be one of the LIMx limit thresholds If instead the alarm must be displayed as a consequence of the a...

Page 9: ...measurements set parameters download events and send collected data via e mail Parameter setting from smartphone or tablet with NFC You can use the Lovato Electric NFC App available for Android tablets and smartphones to program the parameters in a simple intuitive manner without the need for cables and even with the ADXL powered off Simply place the smart device against the ADXL s front panel to ...

Page 10: ...must be set in such a way that the motor starts running slowly immediately after the start command P01 04 With torque control enabled P05 01 ON this parameters determines the time required to reach 100 motor torque and thus sets the acceleration ramp slope If the torque demand from the load is less than 100 the time required to deliver it will be shorter in proportion to keep the slope constant If...

Page 11: ...l input or as PTC sensor input P04 06 This function is used in unsupervised applications with 2 wire motor starting command If the motor is stopped by an alarm with Automatic reset enabled after a time defined in P04 07 the alarm resets and hence the motor starts again If after the reset the motor does not restart a number of motor reset and restarting attempts are made as set During the alarm sta...

Page 12: ... Selected input contact closing delay P06 n 05 Selected input contact opening delay P07 PROGRAMMABLE OUTPUTS OUTn n 1 3 UoM Default Range P07 n 01 Output function OUT1 ALL GLB OUT2 LIN CONT OUT3 RUN see Output functions table P07 n 02 Function index x 1 1 8 P07 n 03 Normal status OFF OFF ON P07 n 04 ON delay sec 0 0 0 6000 0 P07 n 05 OFF delay sec 0 0 0 6000 0 Note This menu is divided into 3 sect...

Page 13: ...eshold remains stored and must be manually reset using the control menu ON or whether it resets automatically OFF P13 USER ALARMS UAn n 1 4 Default Range P13 n 01 Reference value OFF OFF INPx OUTx LIMx REMx P13 n 02 Channel no x 1 OFF 1 99 P13 n 03 Function UAn text 16 characters Note this menu is divided into 4 sections for user alarms UA1 4 P13 n 01 This defines the digital input or internal var...

Page 14: ... bypass A09 MOTOR LOAD TOO LOW Motor load torque lower than setting during bypass A10 STARTING TOO LONG Starting time from start to bypass longer than setting A11 BYPASS RELAY FAULT Bypass relay contacts did not close or open A12 MOT THERMAL WARNING Imminent motor protection trip with motor in bypass A13 STARTER TH WARNING Imminent soft starter protection trip A14 MOTOR THERMAL TRIP Motor thermal ...

Page 15: ...input Used as a source for user alarms for instance 11 CONTROL Runs the Cx commands menu The number of the command to be executed is x set in P06 n 02 Programmable inputs default settings The following table gives the factory default settings for the programmable inputs If necessary these settings can be changed with menu P06 Programmable inputs INPUT TERMINALS DEFAULT FUNCTION INP1 IN1 START INP2...

Page 16: ...ST LOW POWER MOTOR ADVANCED Test with low power motor Ignores current related alarms for a bench test with low power motors Installation Recommendations Switch off power to the soft starter every time you need to work on the electrical or mechanical equipment of the system or machine A disconnecting device such as switch disconnector line contactor etc must always be included to cut off the power ...

Page 17: ...485 communications interface code EXC1042 2 wire starting Motor PTC connection Starting with reversible rotation Timer delayed at de energisation code TMD 2 T1 1 L1 4 T2 6 T3 3 L2 5 L3 A1 FU1 QF1 PROG OUT A2 A1 QS2 11 14 12 21 24 34 FAN FAN C IN1 IN2 IN3 PROG IN KM1 A B RS485 OUT1 OUT2 OUT3 2 KM1 KM2 KM2 KM1 SB4 SB2 KM2 KM1 OUT2 KM2 SB2 SB4 KM1 KM2 T1 ...

Page 18: ...Doc I456GB06_16 docx 29 06 2016 p 18 20 Mechanical dimensions ADXL0030 ADXL0045 ADXL0060 ADXL0075 ADXL0085 ADXL0115 Terminal layout A1 A2 11 14 12 21 24 34 C IN1 IN2 IN3 FAN ...

Page 19: ... FWP 80B 80FE ADXL 0045 600 125 5 600 FWP 125A 120FEE ADXL 0060 600 160 5 600 FWP 150A 160FEE ADXL 0075 600 250 10 600 FWP 175A 180FEE ADXL 0085 600 315 10 600 FWP 200A 200FEE ADXL 0115 600 400 10 600 FWP 250A 250FM ADXL 0135 600 450 10 600 FWP 300A 315FM ADXL 0162 600 500 10 600 FWP 500A 500FMM ADXL 0190 600 630 10 600 FWP 600A 630FMM ADXL 0250 600 700 18 600 FWP 700A 700FMM ADXL 0320 600 800 18 ...

Page 20: ...g IEC EN 60068 2 27 Vibration resistance 0 7g IEC EN 60068 2 6 Supply relay connections Terminal types Screw type fixed Wire cross section min and max 0 2 4 mm2 26 10 AWG Tightening torque 0 8 Nm 7 lbin Fan supply and digital input connections Terminal types Screw type fixed Wire cross section min and max 0 2 2 5 mm2 24 12 AWG Tightening torque 0 44 Nm 4 lbin Power connections Terminal types Fixed...

Reviews: