“07” КОНТРОЛЬ ГЕНЕРАТОРА 

По

 

у мо л ч

Пределы

 

“07” GEN CONTROL 

Р0701 минимальное пороговое значение напряжения (%) 

80 

70-100 

P0701 MIN voltage limit (%) 

Р0702 задержка сигнала минимума напряжения (сек) 

0-600 

P0702 MIN voltage delay (sec) 

Р0703 максимальное пороговое значение напряжения (%) 

115 

100-120 

P0703 MAX voltage limit (%) 

Р0704 задержка сигнала максимума напряжения (сек) 

0-600 

P0704 MAX voltage delay (sec) 

Р0705 время стабилизации параметров генератора (сек) 

20 

0-600 

P0705 Generator into limits delay (sec) 

Р0706 гистерезис пределов мин/макс (%) 

3.0 

0.0-5.0 

P0706 MIN/MAX hysteresis limit (%) 

Р0707 предельное значение асимметрии фаз (%) 

15 

5-20 

P0707 MAX asymmetry limit (%) 

Р0708 задержка сигнала асимметрии фаз (сек) 

0-600 

P0708 MAX asymmetry delay (sec) 

Р0709 максимальное значение частоты (%) 

110 

100-120/OFF 

P0709 MAX frequency limit (%) 

Р0710 задержка сигнала макс частоты (сек) 

0-200 

P0710 MAX frequency delay (sec) 

Р0711 минимальное значение частоты (%) 

90 

OFF/80-100 

P0711 MIN frequency limit (%) 

Р0712 задержка сигнала мин частоты (сек) 

0-600 

P0712 MIN frequency delay (sec) 

Р0713 контроль генератора отключен / внутренний / 
внешний 

INT 

OFF/INT/EXT 

P0713 Gen. Control (OFF/internal/external) 

P0714

 

A27

 

A28

 ЗАДЕРЖКА СИГНАЛА

(

SEC

240 

5-240 

P0714 A27 A28 alarms delay (sec)

 

 

 

 

 

 

Note!

 Контроль чередования фаз доступен через меню свойств сигнала. 

Это возможно когда напряжение > 50VAC. 

 

Note!

 The phase sequence control can be enabled by means of the alarm 

properties menu. 
It is enabled only when the three phase voltages are > 50VAC.  

 

“08” ЗАЩИТА ГЕНЕРАТОРА 

По

 

у мо л ч

Пределы

 

“08” GENERATOR PROTECTION 

Р0801 номинальный ток генератора (А) 

OFF 

OFF/5-10000 

P0801 Rated generator current (A) 

Р0802 максимальное пороговое значение тока (%)  

OFF 

100-500/OFF 

P0802 MAX current limit (%) 

Р0803 задержка сигнала максимума тока (сек)  

0.0-60.0 

P0803 MAX current delay (sec) 

Р0804 выбор характеристической кривой тепловой защиты  

OFF 

(1) 

P0804 Thermal protection curve selection 

Р0805 время срабатывания защиты генератора (сек) 

60 

0-5000 

P0805 Generator protection reset time 
(sec) 

 

(1) 

Для установки класса защиты, проверьте возможные параметры в 

программном обеспечении. 

Внимание!! 

Ток

 

внешнего трансформатора может быть выбран 

параметрами P0802 и P0804. 

 

(1) 

Before setting the protection class, it is advisable to check the trip 

characteristic by means of the set-up software. 

Caution!! 

The external CT must be chosen on the basis of the maximum 

current defined by the parameters P0802 and P0804. 

 

“09” TEST AND MAINTENANCE 

По

 

у мо л ч

Пределы

 

“09” TEST AND MAINTENANCE 

 

 

 

 

Р0901 день начала тестирования 1 1-7 

Lunedi

Monday 

Lun...Dom. 

Mon...Sun. 

P0901 TEST beginning day 

Р0902 время начала тестирования (часы)  

12 

00-23 

P0902 TEST beginning hour (h) 

Р0903 время начала тестирования (минуты)  

00 

00-59 

P0903 TEST beginning minutes (min) 

Р0904 интервал между тестированием (дни)  

1-30 

P0904 Interval between TESTS (days) 

Р0905 время выполнения тестирования (мин)  

OFF 

OFF/1-60 

P0905 TEST duration (min) 

Р0906 тест нагрузки  

OFF 

OFF/ON/

 ВЫКЛ-Х.Х

  P0906 Test with load 

Р0907 интервал техобслуживания (часы)  

OFF 

OFF/1-999 

P0907 Maintenance interval (h) 

Р0908 автоматический тест с внешним остановом 

OFF 

OFF/ON 

P0908 Automatic test with external stop 

 
 
 
 
 
 
 

“10” 

ПАРАМЕТРЫ ПОРТА

 

По

 

у мо л ч

Пределы

 

“10” COMMUNICATION PORT

 

 

 

 

 

Р1001 адрес устройства в сети 1 1 

1-99 

P1001 Serial port address 

Р1002 скорость передачи данных порта RS 

9600 

OFF/1200-38400  P1002 RS-232 baud rate 

Р1003 скорость передачи данных порта RS 

OFF 

OFF/1200-38400  P1003 RS-485 baud rate 

Р1004 модемный канал RS 

RS232 

RS232/RS485 

P1004 Modem channel 

P1005 Паритет 

0=no 

1=pari/even 

2=dispari/odd 

P1005 Parity 

P1006 RS232 протокол 

0=Lovato 

1=Modbus RTU 

P1006 RS232 protocol 

P1007 RS485 протокол 

0=Lovato 

1=Modbus RTU 

P1007 RS485 protocol 

 

Внимание!

 Порты RS232 и RS485 могут использоваться одновременно, 

однако запрещено одновременно программировать прибор через оба 

порта.. 

 

Caution!

 The RS232 and RS485 ports can be used at the same time, but it is  

forbidden to simultaneously do set-up operations with both ports. 

 

“11” ПРОЧИЕ ПАРАМЕТРЫ

 

По

 

у мо л ч

Пределы

 

“11” MISCELLANEOUS

 

 

 

 

 

Р1101 максимальная мощность двигателя при старте  

OFF 

OFF/ON 

P1101 Start threshold Kw 

Р1102 пороговое значение мощности запущенного 

двигателя (кВт) 

0-9999 

P1102 Engine start threshold (kW) 

Р1103 задержка порогового значения запуска (сек)  

0-999 

P1103 Engine start threshold delay (sec) 

Р1104 пороговое значение мощности 
останавливающегося двигателя (кВт) 

0-9999 

P1104 Engine stop  threshold (kW) 

Р1105 задержка порогового значения останова (сек)  

0-999 

P1105 Engine stop  threshold delay (sec) 

Р1106 ненагруженный генератор (отсутствие нагрузки)  

OFF 

OFF/ON 

P1106 Dummy load 

Summary of Contents for RGK 50

Page 1: ...a of the selected data page or to modify the parameters OFF RESET MAN AUT and TEST keys Press these keys to select the operating mode The illuminated LED indicates the selected operating mode if it is...

Page 2: ...le within preset limits When the LED of the changeover symbol is on the actual closing of switching devices has occurred when flashing there is an incorrect feedback signal for the actual closing or o...

Page 3: ...is immediately stopped if running by changing to this operating mode and any eventual alarms are reset If the cause of the alarm is still present it cannot be reset MAN mode The engine can be manuall...

Page 4: ...release the OFF RESET key User s menu Access to parameters setting limited to those the final user needs To enter the menu press the OFF RESET key for 5 seconds then release it Commands menu Access t...

Page 5: ...n to the screen page with data alarms measurements etc This page can contain details convenient to the user such as customer s name date of panel or genset manufacture set up file name serial number o...

Page 6: ...ing To set the engine hour counter press the OFF RESET key and subsequently the ENTER and keys for 5s after that release them Set the counter using the or key and press the EXIT key to store and exit...

Page 7: ...nected sec P0215 OFF OFF 1 30000 P0215 Fuel tank capacity P0216 LL LL LN LL N P0216 Voltage control P0217 1 0 600 P0217 Motorised circuit breaker opening sec P0218 1 0 600 P0218 Motorised circuit brea...

Page 8: ...ble to check the curve characteristic by means of the set up software 06 RGK 60 06 MAINS CONTROL Only for RGK 60 0601 85 70 100 P0601 MIN voltage limit 0602 5 0 600 P0602 MIN voltage delay sec 0603 11...

Page 9: ...by means of the set up software Caution The external CT must be chosen on the basis of the maximum current defined by the parameters P0802 and P0804 09 TEST AND MAINTENANCE 09 TEST AND MAINTENANCE 09...

Page 10: ...GK 60 25min 0 99 P1113 Start engine delay RGK 60 only EJP 1114 RGK 60 5min 0 30 P1114 Changeover delay RGK 60 only 1115 RGK 60 OFF OFF ON P1115 Changeover block RGK 60 only P1116 OFF OFF 1 600 P1116 D...

Page 11: ...Disabled 1 P1207 Input terminal 8 7 8 7 NO NO NC 8 7 Type of contact 8 7 0 0 0 0 6000 0 8 7 Closing delay s 8 7 0 0 0 0 6000 0 8 7 Opening delay s P1208 8 8 Disabled 1 P1208 Input terminal 8 8 8 8 NO...

Page 12: ...lobal alarm 1 P1301 Output terminal 5 3 5 4 5 5 Function 5 3 Relay 1302 6 2 Siren 1 P1302 Output terminal 6 2 Function 6 2 Relay 1303 6 3 Decelerator 1 P1303 Output terminal 6 3 Function 6 3 Relay 130...

Page 13: ...g RGK 60 only RGK 60 Mains motorised circuit breaker closing RGK 60 only Generator motorised circuit breaker opening Generator motorised circuit breaker closing Valve preheating 1 Relay 1 set reset vi...

Page 14: ...inputs N B 1 See the list of the available functions in the Programmable inputs table N B Refer to the setting mode of standardinputs for the property of these inputs 15 15 PROGRAMMABLE OUTPUTS EXPANS...

Page 15: ...efficient battery A17 X X X X X X X A1 7 Charger alternator failure A18 X X X X X A1 8 W signal failure 1 A19 W X X X X X A1 9 Low engine W speed 1 A20 W X X X X X X A2 0 High engine W speed 1 A21 X X...

Page 16: ...erature analog sensor A47 A47 Battery charger alarm UA1 1 UA1 User s alarm 1 UA2 2 UA2 User s alarm 2 UA3 3 UA3 User s alarm 3 UA4 4 UA4 User s alarm 4 UA5 5 UA5 User s alarm 5 UA6 6 UA6 User s alarm...

Page 17: ...age A15 A1 5 Low battery voltage A16 A1 6 Inefficient battery A17 A1 7 Charger alternator failure A18 A1 8 W signal failure 1 A19 W A1 9 Low engine W speed 1 A20 W A2 0 High engine W speed 1 A21 A2 1...

Page 18: ...1 UA1 User s alarm 1 UA2 2 UA2 User s alarm 2 UA3 3 UA3 User s alarm 3 UA4 4 UA4 User s alarm 4 UA5 5 UA5 User s alarm 5 UA6 6 UA6 User s alarm 6 UA7 7 UA7 User s alarm 7 UA8 8 UA8 User s alarm 8 1 W...

Page 19: ...ENERATORE CONTATTORE RETE 2 4 4 1 4 3 4 2 TA2 TA1 3 1 3 2 3 3 3 4 INGRESSI CT1 CORRENTE CT2 CURRENT INPUTS LIBERO FREE FREE FREE GENERATOR OVERLOAD GENERATOR CONTACTOR MAINS CONTACTOR REMOTE START FRE...

Page 20: ...0 4 10 2 1 3 L1 1 1 1 2 RETE TENSIONE 2 1 1 4 N L1 2 2 2 3 GENERATORE TENSIONE 6 2 6 4 6 5 6 3 6 1 5 1 5 3 5 2 4 4 CONT GENERATORE CONTATTORE RETE 2 4 4 1 4 3 4 2 TA1 3 1 3 2 3 4 3 3 INGRESSO CORRENTE...

Page 21: ...APRISA ALTERNATORI TIPO ELETTROVALVOLA CARBURANTE DUCATI SAPRISA ALTERNATOR TYPE BATTERY W SPEED INPUT FUEL SOLENOID VALVE BATTERIA DECELERATOR SIREN START 6 5 B 10 4 7 2 7 1 6 6 10 2 10 3 10 1 SIRENA...

Page 22: ...typical 2 9V 5 3V t 4 3V Input high voltage 5 3V typical 4 3V 50ms Input delay 50ms W Speed input W AC Input type AC coupling 5 50Vpp Voltage range 5 50Vpp 40 2000Hz Frequency range 40 2000Hz 500rpm E...

Page 23: ...A 12VDC 130mA 24VDC 4 1 4 2 4 3 4 4 Relay output 4 1 4 2 4 3 4 4 terminals voltage free 1 1 RGK 60 Contact type 1 NC for mains for RGK 60 only And 1 NO for generator UL B300 30VDC 1A UL Rating B300 30...

Page 24: ...0k L N 1 2 3 Wiring mode 1 2 or 3 phases with or without neutral Current inputs Ie 5A Rated current Ie 5A 0 02 6A Measuring range 0 02 6A UL Max 5 A UL rating Supplied by an external current transform...

Page 25: ...EN 60068 2 6 LROS Lloyd s Register Of Shipping IEC EN 60068 2 52 RINA Italian Naval Register UL 508 and CSA C22 2_N14 95 cULus IEC EN 61010 1 IEC EN 55011 EN 50082 2 IEC EN 60028 2 61 IEC EN 60068 2...

Reviews: