background image

9

 

 

 

 

ALARM INDICATIONS

 

– 

In the event of an anomaly, the PMVF  60 indicates the situation with a pop-up window.

 

– 

If the user presses buttons on the front, the alarm is hidden temporarily to permit consultation of the screens.

 

– 

The alarm remains while the anomaly is present.

 

 

CODE

 

ALARM / INDICATION

 

DESCRIPTION / POSSIBLE CAUSES

 

A02

 

IS OPENING FAILURE

 

The IP sends the opening command to the IS, but the auxiliary (feedback) contact is closed, so the IP sends an  opening command to the 
backup.

 

Check the operation of the IS and of its auxiliary (feedback) contact.

 

A03

 

IS CLOSING FAILURE

 

– 

The IP has ordered the closing of the IS but it does not close (check OUT1 wiring and/or IS coil).

 

– 

The auxiliary IS contact (feedback) is not working.

 

– 

The auxiliary IS contact (feedback) is not connected correctly to terminal INP1.

 

– 

The auxiliary IS contact (feedback) is not fitted since it is not envisaged in the scheme.

 

Disable alarm A03 by setting P06.03 to OFF.

 

Note: LOVATO Electric recommends the use of the feedback input.

 

A04

 

INCORRECT MODULE HW CONFIGURATION

 

PMVF  60 has not found the required expansion modules. Check that they are configured correctly at the side as in the  figure on page 11.

 

A05

 

LSP1 TRIP - PRESS 

▲ ▼

 TO RESTORE

 

Power Imbalance Limit protection LSP1 has tripped. Automatic 
time-based or manual reset.

 

A06

 

LSP2 TRIP - PRESS 

▲ ▼

 TO RESTORE

 

Power Imbalance Limit protection LSP2 has tripped. Automatic 
time-based or manual reset.

 

 

– 

All the alarms/warnings except A04 are non-retentive, i.e. they reset when the anomaly is no longer present after the corresponding reset times.

 

– 

In the presence of a non-retentive alarm, the equipment continues to operate in any case.

 

– 

Exit OUT4 can be programmed to indicate the presence of any alarm (global alarm function).

 

 

 

SELF-DIAGNOSIS

 

– 

The PMVF  60 features a series of self-diagnosis checks. If any of these checks is unsuccessful, a window displaying the text System Error Exx is displayed, where xx indicates the reason for malfunction. Should  this indication occur, contact our Customer 
Service office (Tel. + 39 035 4282422; E-mail: [email protected]), stating the code indicated.

 

 

 

CURRENT, POWER AND ENERGY MEASUREMENTS

 

– 

If CTs are connected to the current inputs and their reading is enabled by setting parameter P01.04 to a value other than OFF, the equipment will measure currents, powers and energies that, depending on where  the CTs are positioned may refer to energy 
exchange (CTs positioned on the delivery point) or to the energy produced (CTs positioned on the genset line).

 

– 

The active power produced (exported, i.e. transferred to the grid) 

will be displayed with conventional minus sign 

(e.g. 

 6.5 kW). The quantity of energy produced by the genset will be added to the exported energy meter.

 

 

 

 

–  There is also a page called Trend Graph which displays the trend in energy production in the last 24 hours (see below). 

 

 

– 

The power measurements permit monitoring of the genset production parameters and making them available on the display or to any supervision system that can read them through one of the supported optional  communication modules.

 

 

 

POWER IMBALANCE LIMIT (LSP) CONTROL

 

– 

In three-phase+neutral systems, with CTs installed, the PMVF  60 can also be programmed to carry out the Power Imbalance Limit (LSP) function..

 

– 

In this case, when an imbalance is measured between the phase active powers (difference between the highest and lowest powers) of more than 6 kW for a time > 30 mins or an imbalance of more than 10 kW for  a time > 1 min, LSP protection trips.

 

 

 

 

 

– 

This protection can be programmed to open relay OUT3 or to open the IS via output OUT1.

 

– 

See set-up parameters P01.09 to P01.14 (MENU M01 - GENERAL on page 6).

 

– 

LSP protection tripping is highlighted by A05 and A06 appearing on the display (for LSP1=6 kW and LSP2=10 kW imbalance thresholds respectively).

 

– 

It is possible to restore manually by pressing the 

▲ ▼

 buttons simultaneously, or automatically by waiting for the time set with P01.14.

 

I48

GB

 09

 16

 

31

10

02

98

 

Total produced 

energy 

Power 

Negative = exported = produced 

Positive = imported = consumed 

Imported/Exported 

indication 

Scale in hours 

with respect to the 

current time 

Active power 

produced 

Scale in kW 

Summary of Contents for PMVF 60

Page 1: ...die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftung f r die elektrische Sicherheit Die...

Page 2: ...Nrail 6units LCDgraphic128x80pixel backlit 4greylevels 4displayandsettingbuttons Voltage measuring inputs three phase neutral Possibilityofoperationinthefollowinglineconfigurations Three phase with ne...

Page 3: ...inactivestate Threepageswithtripprotectioncountersfollow dividedintototaltripcount voltagethresholdtripcountandfrequencythresholdtripcount The counters can be reset through the Commands Menu Inthepage...

Page 4: ...AYSIN USE V F THRESHOLDS AND DELAYSCURRENTLY ACTIVE 4 IP TRIP COUNTER ISTRIPCNT BACKUPTRIPCNT 5 VOLTAGETHRESHOLDTRIPCOUNTERS CNT 59 2 CNT 59 1 CNT 27 1 CNT 27 2 6 FREQUENCYTHRESHOLDTRIPCOUNTERS CNT81...

Page 5: ...enu thenselectthepasswordiconandpressV Thepasswordsettingwindowshownbelowwillappear Pressthe buttonstochangethevalueoftheselecteddigit Pressthe buttontoconfirmthedigitandcycletothenextones Enterthepas...

Page 6: ...OFF 1 0 20 0 P01 13 LSP delay time 2 s 60 1 3600 P01 14 Automatic LSP restore time min 5 OFF 1 60 P01 15 OUT4 output function Global Alarm OFF IS Backup LSP Global Alarm Threshold 59 1 Threshold 59 2...

Page 7: ...P04 01 V MAX 59 2 Threshold 115 100 130 P04 02 V MAX 59 1 Threshold 110 100 120 P04 03 V MIN 27 1 Threshold 85 20 100 P04 04 V MIN 27 2 Threshold 40 5 100 P04 05 V MAX 59 2 Delay s 0 20 0 05 1 00 P04...

Page 8: ...perform occasional operations like resetting measurements counters alarms etc IftheAdvanced levelaccesspasswordwasentered theCommandsMenucanalsobeusedtoperformautomaticoperationsusefulforconfiguringt...

Page 9: ...alfunction Should this indication occur contact our Customer Service office Tel 39 035 4282422 E mail service LovatoElectric com stating the code indicated CURRENT POWER AND ENERGY MEASUREMENTS IfCTsa...

Page 10: ...S2terminalsareconnectedtoeachotherinternally The auxiliary IS contact feedback must of necessity be connected InthecaseofmultipleISs theISfeedbackcontactmustbeaparallelconnectionofalltheISs auxiliaryc...

Page 11: ...22 BACKUP ACTIVATION MODES 14 12 24 22 24 22 24 Note The default backup control mode is A If mode D is selected Backup output mirrors the IS output See parameter P01 16 M01 GENERALMENU on page 6 TERMI...

Page 12: ...ls 2 4forsupply 4 for voltage measurement Cablecrosssection min max 0 2 4 0mm2 24 12AWG Tightening torque 0 8Nm 7lbin Terminaltype Screw type fixed No ofterminals 6 Cablecrosssection min max 0 2 2 5mm...

Reviews: