M05 – COMMUNICATION

 

UoM

 

Default

 

Range

 

P05.01

 

Serial node address

 

 

01

 

01-255

 

P05.02

 

Serial speed

 

bps

 

9600

 

1200

 

2400

 

4800

 

9600

 

19200

 

38400

 

57600

 

115200

 

P05.03

 

Data format

 

 

8 bit – n

 

8 bit, no parity 

8 bit, odd

 

8 bit, even

 

7 bit, odd

 

7 bit, even

 

P05.04

 

Stop bits

 

 

1

 

1-2

 

P05.05

 

Protocol

 

 

Modbus RTU

 

Modbus  RTU 
Modbus ASCII 

Modbus TCP 

P05.06

 

IP address

 

 

000.000.000.000

 

000.000.000.000 -

 

255.255.255.255

 

P05.07

 

Subnet mask

 

 

000.000.000.000

 

000.000.000.000 -

 

255.255.255.255

 

P05.08

 

IP port

 

 

1001

 

0-9999

 

P05.09

 

Gateway function

 

 

OFF

 

OFF/ON

 

 

P05.01 

– Serial address (node) for the communication protocol.

 

P05.02 

– Communication port bitrate.

 

P05.03 

– Data format. 7 bit setting position for ASCII protocol only.

 

P05.04 

– Number of stop bits.

 

P05.05 

– Communication protocol selection.

 

P05.06, P05.07, P05.08 

– TCP/IP details for applications with Ethernet interface. Not used with other communication module types.

 

P05.09 

– Gateway function enable.

 

 

M06 –  ALARMS

 

UoM

 

Default

 

Range

 

P06.01

 

Alarm A01 enable

 

 

ON

 

ON - OFF

 

P06.02

 

Alarm A02 enable

 

 

ON

 

ON - OFF

 

P06.03

 

Alarm A03 enable

 

 

ON

 

ON - OFF

 

P06.04

 

Alarm A04 enable

 

 

ON

 

ON - OFF

 

P06.05

 

Alarm A05 enable

 

 

ON

 

ON - OFF

 

P06.06

 

Alarm A06 enable

 

 

ON

 

ON - OFF

 

 

P06.01…P06.06 

– Enables or disables the corresponding alarm.

 

Note: 

The use of the auxiliary feedback contact on the IS is recommended even in applications where the backup device is not used. If not even the feedback contact is used however, it will be necessary to  deactivate alarm A03 by setting P06.03 to OFF.

 

 

 

COMMANDS MENU

 

– 

The Commands Menu is used to perform occasional operations, like resetting measurements, counters, alarms, etc.

 

– 

If the Advanced-level access password was entered, the Commands Menu can also be used to perform automatic operations useful for configuring the instrument.

 

– 

The following table shows the functions which are available with the Commands Menu, divided according to the required access level.

 

 

CODE

 

COMMAND

 

ACCESS 

LEVEL

 

DESCRIPTION

 

C.01

 

RESET HI-LO

 

User / Advanced

 

Resets the HI and LO values of all measurements

 

C.02

 

RESET TRIP COUNTERS

 

User / Advanced

 

Resets the trip counters

 

C.03

 

RESET PARTIAL ENERGY METERS

 

User / Advanced

 

Resets partial energy meters.

 

C.11

 

RESET TOTAL ENERGY METER

 

Advanced

 

Resets total and partial energy meters and tariffs

 

C.12

 

PARAMETERS TO DEFAULT

 

Advanced

 

Restores all settings to factory default values

 

C.13

 

PARAMETER BACKUP

 

Advanced

 

Saves a backup copy of the settings

 

C.14

 

PARAMETERS   RESTORE

 

Advanced

 

Reloads the settings from the backup copy

 

C.15

 

TEST THRESHOLD 27-2

 

Advanced

 

Temporarily shifts threshold 27-1 to permit testing of threshold 27-2. See note below.

 

Note: 

The purpose of command C.15 is to permit testing of threshold 27-2 via relay test kit. This threshold is normally “covered” by 27-1 and consequently cannot be tested according to the procedures indicated by the standard. Giving this command sets 

threshold 27-1 temporarily to the minimum permitted value (20% Un), lower than the default value of 27-2 (40%Un) so as to permit it to be tested. This shift in the threshold lasts for a maximum of 5 minutes, during which the shifted value is visible on the 
Active Thresholds page. Switching the PMVF 60 off then on or waiting for the period to elapse (sufficient for performing the test) brings threshold 27-1 back to its normal set value.

 

I48

GB

 09

 16

 

31

10

02

98

 

Summary of Contents for PMVF 60

Page 1: ...die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftung f r die elektrische Sicherheit Die...

Page 2: ...Nrail 6units LCDgraphic128x80pixel backlit 4greylevels 4displayandsettingbuttons Voltage measuring inputs three phase neutral Possibilityofoperationinthefollowinglineconfigurations Three phase with ne...

Page 3: ...inactivestate Threepageswithtripprotectioncountersfollow dividedintototaltripcount voltagethresholdtripcountandfrequencythresholdtripcount The counters can be reset through the Commands Menu Inthepage...

Page 4: ...AYSIN USE V F THRESHOLDS AND DELAYSCURRENTLY ACTIVE 4 IP TRIP COUNTER ISTRIPCNT BACKUPTRIPCNT 5 VOLTAGETHRESHOLDTRIPCOUNTERS CNT 59 2 CNT 59 1 CNT 27 1 CNT 27 2 6 FREQUENCYTHRESHOLDTRIPCOUNTERS CNT81...

Page 5: ...enu thenselectthepasswordiconandpressV Thepasswordsettingwindowshownbelowwillappear Pressthe buttonstochangethevalueoftheselecteddigit Pressthe buttontoconfirmthedigitandcycletothenextones Enterthepas...

Page 6: ...OFF 1 0 20 0 P01 13 LSP delay time 2 s 60 1 3600 P01 14 Automatic LSP restore time min 5 OFF 1 60 P01 15 OUT4 output function Global Alarm OFF IS Backup LSP Global Alarm Threshold 59 1 Threshold 59 2...

Page 7: ...P04 01 V MAX 59 2 Threshold 115 100 130 P04 02 V MAX 59 1 Threshold 110 100 120 P04 03 V MIN 27 1 Threshold 85 20 100 P04 04 V MIN 27 2 Threshold 40 5 100 P04 05 V MAX 59 2 Delay s 0 20 0 05 1 00 P04...

Page 8: ...perform occasional operations like resetting measurements counters alarms etc IftheAdvanced levelaccesspasswordwasentered theCommandsMenucanalsobeusedtoperformautomaticoperationsusefulforconfiguringt...

Page 9: ...alfunction Should this indication occur contact our Customer Service office Tel 39 035 4282422 E mail service LovatoElectric com stating the code indicated CURRENT POWER AND ENERGY MEASUREMENTS IfCTsa...

Page 10: ...S2terminalsareconnectedtoeachotherinternally The auxiliary IS contact feedback must of necessity be connected InthecaseofmultipleISs theISfeedbackcontactmustbeaparallelconnectionofalltheISs auxiliaryc...

Page 11: ...22 BACKUP ACTIVATION MODES 14 12 24 22 24 22 24 Note The default backup control mode is A If mode D is selected Backup output mirrors the IS output See parameter P01 16 M01 GENERALMENU on page 6 TERMI...

Page 12: ...ls 2 4forsupply 4 for voltage measurement Cablecrosssection min max 0 2 4 0mm2 24 12AWG Tightening torque 0 8Nm 7lbin Terminaltype Screw type fixed No ofterminals 6 Cablecrosssection min max 0 2 2 5mm...

Reviews: