4
–
For many pages, the
button permits access to sub-pages (for example, to display the maximum and minimum values recorded).
–
The sub-page displayed currently is indicated at the bottom left by one of the following icons:
•
IN = Instantaneous value
– Current instantaneous value of the measurement, displayed by default every time the page is changed.
•
HI = Maximum instantaneous value
– Highest value measured by the IP for the corresponding measurement. HIGH values are stored and preserved even in the absence of a power supply. They can be reset through a dedicated command (see
COMMANDS MENU on page 8).
•
AV = Average value
– Average value of the measurements, with slowed variations (average of the last minute).
•
LO = Minimum instantaneous value
– Lowest value measured by the IP from the moment voltage is applied. It is reset with the same command used for the HI values.
•
GR = Graphic bars
– Display of measurements through graphic bars.
–
The user can specify the page and sub-page to return to automatically after no buttons have been pressed for a given time.
–
It is also possible to program the PMVF 60 so that the display always remains that which was last selected.
–
For the set-up of these functions, see MENU M02 – UTILITY on page 7.
TABLE OF DISPLAY PAGES
No.
Selection via
▲
and
▼
PAGES
Selection via
SUB-PAGES
1
VOLTAGES, FREQUENCY
V(L1-L2), V(L2-L3), V(L3-L1), F(Hz)
HI
LO
AV
GR
2
IP STATE OVERVIEW
STATE OF IS/BACKUP CONTROL OUTPUTS, FEEDBACK INPUT, EXTERNAL SIGNAL, IP DISABLING INPUT, REMOTE TRIPPING
3
ACTIVE THRESHOLDS – DELAYS IN USE
V/F THRESHOLDS AND DELAYS CURRENTLY ACTIVE
4
IP TRIP COUNTER
IS TRIP CNT, BACKUP TRIP CNT
5
VOLTAGE THRESHOLD TRIP COUNTERS
CNT 59-2,CNT 59-1,CNT 27-1,CNT 27-2
6
FREQUENCY THRESHOLD TRIP COUNTERS
CNT 81>-2, CNT 81>-1, CNT 81<-1, CNT 81<-2
7
PHASE-TO-PHASE VOLTAGES
V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
HI
LO
AV
GR
8
PHASE-TO-NEUTRAL VOLTAGES
V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
HI
LO
AV
GR
9
MOVING AVERAGE VOLTAGE
VM(L1-L2), VM(L2-L3), VM(L3-L1)
HI
LO
10
PHASE AND NEUTRAL CURRENTS
I(L1), I(L2), I(L3), I(N)
HI
LO
AV
GR
11
ACTIVE POWER
P(L1), P(L2), P(L3), P(TOT)
HI
LO
AV
GR
12
ACTIVE POWER IMBALANCE
kWP1-P2, kWP2-P3, kW P3-P1
HI
LO
AV
GR
13
TREND GRAPH
P(TOT) LAST 24h
14
ACTIVE ENERGY – ACTIVE POWER – BAR GRAPH
kWh (TOT) – kW (TOT) – BAR GRAPH kW(TOT)
15
REACTIVE POWER
Q(L1), Q(L2), Q(L3), Q(TOT)
HI
LO
AV
GR
16
APPARENT POWER
S(L1), S(L2), S(L3), S(TOT)
HI
LO
AV
GR
17
POWER FACTOR
PF(L1), PF(L2), PF(L3), PF(TOT)
HI
LO
AV
GR
18
ENERGY METERS
kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
PARTIAL
19
ENERGY METERS PHASE L1
kWh+L1(TOT), kWh-L1(TOT)
PARTIAL
20
ENERGY METERS PHASE L2
kWh+L2(TOT), kWh-L2(TOT)
PARTIAL
21
ENERGY METERS PHASE L3
kWh+L3(TOT), kWh-L3(TOT)
PARTIAL
22
EXPANSION MODULES
23
INFO-REVISION-SERIAL NO.
MODEL, REV SW, REV HW, SER. No.
24
LOGO
–
Note:
Some of the pages listed above may not be displayed, if the function displayed is not enabled. For example, if external CTs are not connected and programmed, the pages highlighted in grey are not displayed.
–
Note:
The moving average voltage measurement is not available for the first 10 minutes after switching on or resetting the system. During this time, dashes and a countdown indicating the time left before measurement display are shown.
I48
6
GB
09
16
31
10
02
98