– A load-break switch or circuit breaker
must be included in the electrical
installation of the building.
– It must be installled close by the
equipment and within easy reach of the
operator
– It must be marked the disconnecting
device of the equipment:
IEC/ EN 61010-1 § 6.11.2.
This equipment must be installed by
qualified personnel, in compliance with
regulations in force for electrical systems, to
avoid damages or safety hazards.
The pfoducts, illustrated in this document,
are subject to be revised or improved at any
moment. Technical data and descriptions do
not therefore have any contractual value.
Additional errors
Voltage
±0.005% full scale / °C (-20...+60°C)
Current
±0.015% full scale / °C (-20...+60°C)
Insulation
Rated insulation voltage (Ui)
690V
compliant with IEC/EN 61010-1
Ambient conditions
Operating temperature
-20...+60°C
Storage temperature
-30...+80°C
Relative humidity
<90%
Max pollution degree
2
Connections
DMK 20
DMK 50
Terminal type
Plug-in
Fixed
Conductor cross section (min-max)
0.2-2.5 mm
2
0.2-1.5 mm
2
(24-12 AWG)
(24-16 AWG)
Tightening torque
0.5 Nm (4.5 lbin)
0.45 Nm (4 lbin)
Housing
DMK 20
DMK 50
Version
Flush mount per
35mm rail mounting
IEC 61554
EN50022 6x17.5mm
modules
Material
Noryl SE1-GNF2 black
Noryl SE1 grey
self-extinguishing
self-extinguishing
Noryl Noryl
Dimensions w x h x d
96 x 96 x 76mm
105 x 90 x 60mm
Cutout
91 x 91mm
Degree of protection
IP54 on front,
IP41 on front
IP20 on back
IP20 housing and
terminal blocks
Weight
434g
398g
Certifications and compliance
Certifications obtained:
cULus, GOST.
Compliant with standards:
IEC/EN 61010-1, IEC/EN 61000-6-2,
CISPR 11/EN 55011, IEC/EN 61000-3-2,
IEC/EN 61000-3-3, IEC/EN 60068-2-61,
IEC/EN60068-2-27, IEC/EN60068-2-6,
UL508, C22.2 N°14.
UL Marking
– These Devices shall be protected by Any
Listed Fuses, Miscellaneous, Miniature and
Micro (JDYX) 15A Fuses on voltage input
phases.
– “Use 60°C/75°C copper (CU) conductor and
wire size range 18-12 AWG, stranded or
solid”.
– “For use on a flat surface of a Type 1
Enclosure”.
TECHNICAL CHARACTERISTICS
Auxiliary supply
Rated voltage Us
208-240VAC
Operating limits
154-288VAC
Frequency
45-65Hz
Maximum consumption
5.5VA (Us=240VAC)
Maximum dissipation
2.5W (Us= 240VAC)
Immunity time for microbreakings
20ms
Voltage inputs
Maximum rated voltage Ue
690VAC phase-phase
400VAC phase-neutral
UL rating
600VAC phase-phase
347VAC phase-neutral
Measuring range
60-830VAC phase-phase
30-480VAC phase-neutral
Frequency range
45-65Hz
Measuring method
True RMS
Measuring input impedance
>1.1M
phase-phase and >570K
phase-neutral
Wiring mode
Single-phase, two-phase, three-phase and
balanced three-phase.
Current inputs
Rated current Ie
5A (1A on request)
Measuring range
0.05-6A
UL rating
Supplied by an external current transformer
(low voltage). 5A max
Measuring method
True RMS
Overload capacity
+20% Ie from external CT with 5A secondary
Overload peak
50A for 1 second
Dynamic limit
125A for 10ms
Self-consumption
<0.6W per phase
Accuracy
Measuring conditions
Tempe23°C ±1°C
Relative humidity 45±15%
Voltage 0.2 - 1.2 Ue
Current 0.2 - 1.2 Ie
Voltage
Class 0.5 ±0.35% full scale (830VAC)
Current
Class 0.5 ±0.5% full scale (6A)
Frequency
±0.1Hz
Apparent power
±0.5% full scale ±1digit
Active energy
±1% full scale ±1digit (cos
. 0.7 - 1)
±1.25% full scale ±1digit (cos
. 0.3 - 0.7)
Reactive energy
±1% full scale ±1digit (sine
. 0.7 - 1)
±1.25% full scale ±1digit (sine
. 0.3 - 0.7)