Doc: I437GB04_16.docx 09/03/2016
p. 19 / 37
UAx
RALx
P16.n.02
Channel no. (x)
1 1-99
P16.n.03
Multiplier
1 1-1000
P16.n.04
Splitter
1 1-1000
P16.n.05
Counter description
CNTn
(Text - 16 characters)
P16.n.06
Unit of measurement
UMn
(Text - 6 characters)
P16.n.07
Reset source
OFF OFF
ON
INPx
OUTx
LIMx
REMx
PLCx
Axx
UAx
RALx
P16.n.08
Channel no. (x)
1 1-99
Note: This menu is divided into 8 sections for counters CNT1..8.
P16.n.01
- Signal which causes the counter increments (on ramp up). It may be energised by the ATL900 (ON), the exceeding of a threshold (LIMx), the activation
of an external input (INPx), a logical condition (PLCx) etc.
P16.n.02
- Channel number x referred to the previous parameter.
P16.n.03
- Multiplying K. The counted pulse are multiplied by this value before being displayed.
P16.n.04
- Fractioning K. The counted pulse are divided by this value before being displayed. If different from 1, the counter is displayed with two decimal digits.
P16.n.05
- Description of the counter. Free text 16 characters.
P16.n.06
- Counter unit of measurement. Free text 6 characters.
P16.n.07
- Signal which causes the resetting of the counter. The counter remains equal to zero for as long as this signal is active.
P16.n.08
- Channel number x referred to the previous parameter.
M17 - TIMER
(TIMn, n = 1…8)
Unit
Default
Range
P17.n.01
Timer source
OFF
ON
INPx
OUTx
LIMx
REMx
PLCx
Axx
UAx
RALx
P17.n.02
Channel no. (x)
1 1-99
P17.n.03
Delay sec
0 0.0
– 6000.0
Note: This menu is divided into 8 sections for the timers TIM1..8.
P17.n.01 -
Source variable which controls the starting and resetting of the concerned timer.
P17.n.02
- Channel number referred to the previous parameter.
P17.n.03 -
Timer time.
M18 – REMOTE ALARMS
(RALn, n = 1…24)
Unit
Default
Range
P18.n.01
RALn output function
(miscellaneous)
(see Output functions
table )
P18.n.02
Function index (x)
OFF
OFF / 1…99
P18.n.03
Normal/reverse output
NOR
NOR / REV
Note: this menu is divided into 24 sections for state/alarm remoting variables RAL1…RAL24, available in combination with the external unit RGKRR
P18.n.01
- This selects the remote output function RALn. The remote outputs (remote unit relay RGKRR) may assume the same functions as the local outputs,
including the operating states, the alarms etc.
P18.n.02
- Index possibly associated to the function programmed under the previous parameter. Example: If the function of the output is set to the
Alarm Axx
function and this output must be energised when alarm A31 occurs, then P18.n.02 is set to value 31.
P18.n.03
- This sets the output state when the associated function is not active:
NOR
= de-energised output,
REV
= energised output.