Doc: I437GB04_16.docx 09/03/2016
p. 17 / 37
7 bit, odd
7 bit, even
P10.n.04
Stop bit
1
1-2
P10.n.05
Protocol
Modbus RTU
Modbus RTU
Modbus ASCII
Modbus TCP
P10.n.06
IP address
192.168.1.1
000.000.000.000 –
255.255.255.255
P10.n.07
Subnet mask
0.0.0.0
000.000.000.000 –
255.255.255.255
P10.n.08
IP port
1001
0-32000
P10.n.09
Channel function
Slave
Slave
Gateway
Battery charger
P10.n.10
Client / server
Server
Client
Server
P10.n.11
Remote IP address
000.000.000.000 000.000.000.000
–
255.255.255.255
P10.n.12
Remote IP port
1001
0-32000
P10.n.13
IP gateway address
000.000.000.000 000.000.000.000
–
255.255.255.255
These parameters are also accessible with user level password.
Note: This menu is divided into 3 sections for communication channels COM1..3.
The channel COM1 identifies the standard RS-485 port, while COM2 and COM3 are reserved to the possible communication ports on expansion modules
EXP. The infrared frontal programming port has fixed communication parameters and no setting menu is required.
P10.n.01
- Serial address (node) of the communication protocol.
P10.n.02
- Communication port transmission speed (1200 bps not available on slot 1 and 4).
P10.n.03
- Data format. 7-bit settings available for ASCII protocol only.
P10.n.04
- Stop bit number.
P10.n.05
- Communication protocol selection.
P10.n.06, P10.n.07, P10.n.08
- TCP-IP coordinates for applications with Ethernet interface. Not used with other communication module types.
P10.n.09
- Port operating mode.
Slave
= normal operation, the device reply to the messages of an external master.
Gateway
= The device analyses the message
intended to it (serial address) and forwards those address to other nodes through the RS485 interface. See chapter
Communication channels
.
Mirror
= the
communication channel is used to connect a ATL900RD repeater.
P10.n.10
- TCP-IP connection activation.
Server
= Waits for connection from a remote client.
Client
= Establishes the connection towards a remote server. This
parameter also conditions the behaviour of the GSM/GPRS modem. If set to client, the modem attempt a PSD connection towards the remote server/port.
P10.n.11 - P10.n.12 - P10.n.13
- Coordinates for connecting the remote server when P10.n.10 is set to client.
M11 - AUTOMATIC TEST
Unit
Default
Range
P11.01
Automatic TEST enable group 1
OFF
OFF / ON
P11.02
Automatic TEST enable group 2
OFF
OFF / ON
P11.03
Automatic TEST enable group 3
OFF
OFF / ON
P11.04
Interval between TESTS
gg
7 1-60
P11.05
Enable TEST for Monday
ON
OFF / ON
P11.06
Enable TEST for Tuesday
ON
OFF / ON
P11.07
Enable TEST for Wednesday
ON
OFF / ON
P11.08
Enable TEST for Thursday
ON
OFF / ON
P11.09
Enable TEST for Friday
ON
OFF / ON
P11.10
Enable TEST for Saturday
ON
OFF / ON
P11.11
Enable TEST for Sunday
ON
OFF / ON
P11.12
TEST start hour
h
12 00-23
P11.13
TEST start minutes
min
00 00-59
P11.14
TEST time
min
10 1-600
P11.15
Automatic TEST with load switching
OFF OFF
Load
Dummy load
These parameters are also accessible with user level password.
P11.01 - P11.02 - P11.03
- This activate execution of the periodical test of the respective three gensets.
P11.04
- Interval time between one periodical test and the next. If the test is not enabled on the period expiration date, the interval will be extended as a
consequence to the following enabled day.
P11.05
…
P11.11
This enables automatic test execution in the single days of the week. OFF means that the test will not be performed on that day. Caution: The clock
must be set correctly.
P11.12
-
P11.13
This establishes the date and minutes from the beginning of the periodical test. Caution: The clock must be set correctly.
P11.14
- Periodical test time in minutes.
P11.15
– Load management during periodical test execution:
OFF
= The load is not transferred.
Load
= This enables load transfer to the genset.
Dummy load
=
This applies the dummy load while the system load is not switched.
M12– DIGITAL INPUTS
(INPn, n=1…20)
Unit
Default
Range
P12.n.01
INPn input function
(miscellaneous) (see
Input functions
table
)
P12.n.02
Function index (x)
OFF
OFF / 1…99
P12.n.03
Contact type
NO NO/NC
P12.n.04
Closing delay
sec
0.05 0.00-600.00
P12.n.05
Opening delay
sec
0.05 0.00-600.00
Note: This menu is divided into 20 sections for each programmable digital input INP1..INP20.
The inputs on the basic board are numbered from INP1 to INP12, while the remaining number refer to the expansion module inputs.
P12.n.01
- Selection input function selection (see
programmable input function table
).
P12.n.02
- Index possibly associated to the function programmed under the previous parameter. Example: If the input function is set to
Control menu execution Cxx