P09 - MULTIPLE MOTORS (MOTn=1..3) UoM Default Range
P09.n.01
Motor nominal current In A 30.0 15.0…34.5
(100%Ie) (50…105-115%Ie)
P09.n.02
Max (starting) current limit ILt %In 300 150…700
P09.n.03
Step at start % 10 0…100
P09.n.04
Acceleration ramp sec 10 1…120
P09.n.05
Deceleration ramp sec OFF OFF / 1…120
P09.n.06
Deceleration end step % 20 0…100
P09.n.07
Kick start % OFF OFF / 50…100
P09.n.08
Motor nominal cos
0.80 0.50…1.00
Note: This menu is divided into 3 sections for each additional motor MOT1..3.
The motors are selected via the digital inputs configured with the function “multiple motor selection” (MOT. SEL).
P09.n.01 – P09.n.08
- Same meaning as menu P01, referred to multiple motors.
P10 - LIMITS (LIMn, n = 1…4) UoM Default Range
P10.n.01
Reference measure OFF OFF-
(measurements list)
ST. COUNT.
P10.n.02
Channel nr. (x) 1 OFF/1..99
P10.n.03
Function MAX MAX
MIN
MIN+MAX
P10.n.04
Upper threshold 0 -9999 - +9999
P10.n.05
Multiplier x1 /100 – x10k
P10.n.06
Delay sec 0 0.0 - 600.0
P10.n.07
Lower threshold 0 -9999 - +9999
P10.n.08
Multiplier x1 /100 – x10k
P10.n.09
Delay sec 0 0.0 - 600.0
P10.n.10
Normal status OFF OFF-ON
P10.n.11
Latch OFF OFF-ON
Note: This menu is divided into 4 sections for limit thresholds LIM1..4.
P10.n.01
– This defines which measure of the ADXL must be associated to the limit threshold.
P10.n.02
– If the reference measure is a multichannel internal measure, this defines the channel.
P10.n.03
– This defines the limit threshold operating mode.
Max
= LIMn active when the measurement is higher than P10.n.04. P10.n.07 is the resetting threshold.
Min
= LIMn active when the measurement is lower
than P10.n.07. P10.n.04 is the resetting threshold.
Min+Max
= LIMn active when the measurement is higher than P10.n.04 or lower than P10.n.07.
P10.n.04 and P10.n.05
– These define the upper threshold, which is given by the value of P10.n.04 multiplied by P10.n.05.
P10.n.06
– Tripping delay on the upper threshold.
P10.n.07, P10.n.08, P10.n.09
– as above, for the lower threshold.
P10.n.10
– This define the status of the limit LIMn when it is not active.
P10.n.11
– If set to ON, the limit LIMn remains stored and must be manually reset using the Command menu; differently, if set to OFF, the limit LIMn is reset automatically.
P13 - USER ALARMS (UAn, n=1…4) Default Range
P13.n.01
Alarm source OFF OFF
INPx
OUTx
LIMx
REMx
P13.n.02
Channel nr. (x) 1 OFF/1...99
P13.n.03
Description UAn (text - 16 characters)
Note: this menu is divided into 4 sections, for user alarms UA1..4.
P13.n.01
– This defines the source (digital input or internal variable) the activation of which generates the user alarm.
P13.n.02
– Channel number referred to the previous parameter.
P13.n.03
– Free text which will appear in the alarm window.