DUTY LEVEL
APPLICATION PARAMETER DESCRIPTION
LIGHT NORMAL HEAVY
P01.02 MAX CURRENT LIMIT 350% 450% 550%
P01.03 STEP AT START 20% 30% 50%
Centrifugal pump P01.04 ACCELERATION RAMP 5s 10s 10s
P01.05 DECELERATION RAMP 15s 15s 15s
P04.02 START THERMAL CLASS 10 10 15
P05.01 TORQUE CONTROL ON ON ON
P01.02 MAX CURRENT LIMIT 350% 450% 550%
P01.03 STEP AT START 10% 30% 50%
Fire fighting pump P01.04 ACCELERATION RAMP 10s 10s 10s
P01.05 DECELERATION RAMP 15s 15s 15s
P04.02 START THERMAL CLASS OFF OFF OFF
P05.01 TORQUE CONTROL OFF OFF OFF
P01.02 MAX CURRENT LIMIT 350% 450% 550%
P01.03 STEP AT START 10% 30% 50%
Conveyor belt P01.04 ACCELERATION RAMP 10s 10s 30s
P01.05 DECELERATION RAMP 5s 5s 5s
P04.02 START THERMAL CLASS 10 10 15
P05.01 TORQUE CONTROL ON ON ON
P01.02 MAX CURRENT LIMIT 400% 500% 600%
P01.03 STEP AT START 20% 40% 50%
Fan P01.04 ACCELERATION RAMP 20s 30s 60s
P01.05 DECELERATION RAMP OFF OFF OFF
P04.02 START THERMAL CLASS 10 15 20
P05.01 TORQUE CONTROL ON ON ON
P01.02 MAX CURRENT LIMIT 400% 450% 550%
P01.03 STEP AT START 30% 40% 40%
Mixer P01.04 ACCELERATION RAMP 15s 15s 15s
P01.05 DECELERATION RAMP OFF OFF OFF
P04.02 START THERMAL CLASS 10 15 20
P05.01 TORQUE CONTROL OFF OFF OFF
P01.02 MAX CURRENT LIMIT 400% 500% 550%
P01.03 STEP AT START 30% 40% 50%
General purpose P01.04 ACCELERATION RAMP 5s 10s 15s
P01.05 DECELERATION RAMP OFF OFF OFF
P04.02 START THERMAL CLASS 10 10 15
P05.01 TORQUE CONTROL OFF OFF OFF
– In the table below are indicated the parameters which are automatically loaded into the ADXL during the AUTOSET procedure, according to the selected application and duty level.
NAVIGATING THE DISPLAY PAGES
– The
and
buttons allow the measurement display pages to be scrolled one at a time. The current page is shown in text.
– Some of the values may not be displayed, depending on how the starter has been programmed.
– The user can specify to which value the display must return automatically after no buttons have been pressed for a given time.
– The system can be programmed so that the view always remains in the position in which it was left.
– For the set-up of these functions, see the menu P02 – UTILITY.
VALUE DISPLAY UOM
Instantaneous current (highest of three phases) CURRENT A
Instantaneous current as % of nominal motor current CURRENT A %
Phase L1 current (displayed if enabled with parameter P02.07) CURR L1 A
Phase L2 current (displayed if enabled with parameter P02.07) CURR L2 A
Phase L3 current (displayed if enabled with parameter P02.07) CURR L3 A
Motor torque as % of maximum nominal torque TORQUE %
Phase-to-phase line voltage VOLTAGE V
Total active power POWER kW kW
Total PF PF TOT.
Motor thermal status (note: protection trips at > 140%) THERM. ST. %
Starter thyristor temperature INT. TEMP °
Energy in kWh ENER. kWh kWh alternating with value
Motor hour meter HOURS H alternating with value
Start counter ST. COUNT alternating with value
Input/output status (on side bars) INP OUT
LIMx limit variable status LIMITS