      NO.          FUNCTION                                     DESCRIPTION

       0            OFF                                                Output disabled. 

       1            LIN. CONT.                                     Line Contactor: controls the line contactor. It is energised immediately after the start. Remains activated so long as there is voltage to the motor, i.e. during the 

                                                                           acceleration ramp, run, bypass and deceleration ramp. 

       2            RUN                                               Energised when the ramp is completed, with full voltage to the motor. Gives the enable signal to the load.

       3            GLB. ALA                                       Global alarm: one or more alarms with the Global alarm property enabled are active.

       4            LIM                                                Output which represents the status of the limit variable LIMx (x defined by P07.n.02).

       5            REM                                               Output which represents the status of the remote variable REMx (x defined by P07.n.02).

       6            ALA Axx                                         Active when a specific alarm is present (x defined by P07.n.02).

       7            UAxx                                              Active when a specific user alarm is present (x defined by P07.n.02).

PROGRAMMABLE OUTPUT FUNCTIONS TABLE
–   The following table shows all the functions which can be associated to the programmable digital outputs OUTn. 
–   Each output may be configured with normal or reversed function (NOR or REV).
–   Some functions require a further numeric parameter defined by index (x) specified by parameter P07.n.02.
–   See menu P07 Programmable outputs for more details.

  OUTPUT                    TERMINALS                     DEFAULT FUNCTION

    OUT1                        11-14-12                       GLB. ALA  (global alarm)

    OUT2                           21-24                          LIN. CONT (line contactor control)

    OUT3                           21-34                          RUN  (ramp completed)

PROGRAMMABLE OUTPUT DEFAULT SETTINGS
–   The following table reports the factory default settings for the programmable outputs.
–   If necessary, these settings can be changed with menu P07 Programmable outputs. 

    CODE                                          CONTROL                                                                      ACCESS LEVEL                  DESCRIPTION

     C01          MAINTENANCE RESET                                                                                      ADVANCED                      Resets the maintenance interval and resets the alarm

     C02          THERMAL STATUS RESET                                                                                 ADVANCED                      Sets the thermal status to 0%

     C03          START COUNTER RESET                                                                                   ADVANCED                      Resets the number of startings counter

     C04          HOUR METER RESET                                                                                        ADVANCED                      Resets the motor's hour meter

     C05          ENERGY METER RESET                                                                                    ADVANCED                      Resets the energy counters

     C06          LIMITS RESET                                                                                                   ADVANCED                      Resets LIM variables with memory

     C11          REPEAT AUTO SET                                                                                                 USER                          Repeats the AUTOSET wizard

     C12          SETUP TO DEFAULT                                                                                               USER                          Restores the factory default settings

     C13          BACKUP SETUP                                                                                                 ADVANCED                      Saves a copy of the setup parameters 

     C14          RESTORE SETUP                                                                                               ADVANCED                      Restores a copy of the setup parameters

     C15          TEST LOW POWER MOTOR                                                                              ADVANCED                      Test with low power motor – Ignores current-related alarms for a bench test with low power motors

     C16          EVENT LOG RESET                                                                                            ADVANCED                      Resets the memory of the event list

COMMANDS MENU
–   The commands menu is used to perform occasional operations, like resetting of counters, alarms, etc.
–   If the advanced level password was entered, the commands menu can also be used to perform automatic operations useful for configuring the instrument.
–   The following table shows the functions which are available with the commands menu divided according to the required access level.

RECOMMENDATIONS
–   Switch off power to the soft starter every time you need to work on the electrical or mechanical equipment of the system or machine.
–   A disconnecting device, such as switch disconnector, line contactor, etc.  must always be included to cut off the power supply.
–   Never use the soft starter to drive motor power transformers.
–   Do not install the soft starter in areas containing flammable gas or explosives.
–   Do not place the soft starter close to sources of heat.
–   Do not use insulating enclosures since they are poor heat conductors.
–   You can protect the soft starter's SCR properly against short circuit only by using ultra-rapid fuses. To select the fuses, refer to the tables on the last pages of this manual. Note that when the bypass relay is closed

(i.e. motor running), the SCR are protected against short circuit, overload and overvoltage.

POWER FACTOR CORRECTION
–   If power factor correction capacitors are to be used, they must be installed upstream the soft starter, with a contactor and protection fuses. They must be engaged once the starting is terminated, and disengaged

before stopping. The contactor can be controlled with a relay output programmed with function “RUN”.

INSTALLATION

100mm

50mm

50mm

100mm

t < 45°C

t < 45°C

t < 45°C

Summary of Contents for ADXL...

Page 1: ...N 61010 1 6 12 2 1 Clean the instrument with a soft cloth Do not use abrasives liquid detergents or solvents CONTENTS Page Description 2 Front button functions 2 Front LEDs 2 Display indications 2 AUT...

Page 2: ...cation and alarm pre alarm thresholds Advanced self diagnostics NFC interface for programming with smartdevice Integrated frontal optical interface for programming and maintenance Isolated RS485 inter...

Page 3: ...in sequence STEP INFORMATION DEFAULT RANGE 1 Display language ENG ENG ITA FRA ESP POR DEU 2 Nominal motor current 100 ADXL rating 50 100 ADXL rating Example for ADXL 0030 600 Example for ADXL 0030 600...

Page 4: ...02 START THERMAL CLASS 10 10 15 P05 01 TORQUE CONTROL OFF OFF OFF In the table below are indicated the parameters which are automatically loaded into the ADXL during the AUTOSET procedure according to...

Page 5: ...or the status and the electrical variables EXC RDU1 can control up to 32 soft starters ADXL series in contemporary The maximum distance between EXC RDU1 and the more distant soft starter can reach 600...

Page 6: ...gradual acceleration than the torque ramp Together with these two starting methods there is the maximum starting current limitation function Current limit P01 02 If the current delivered by the highe...

Page 7: ...rol board MOTOR THERMAL PROTECTION VIA PTC The ADXL s IN3 input can be configured to connect to a PTC motor thermal protection sensor The trip and reset values are conforming with DIN 44081 Tripping t...

Page 8: ...abort setting the password EVENT LIST The ADXL can store a list of the last 60 events which is stored even in absence of power supply The events stored are the following Power supply on off Start sto...

Page 9: ...given remote functions for instance to generate alarms or messages remotely USER ALARMS UAx The user can define up to 4 programmable alarms UA1 UA4 For each alarm you can configure the source i e the...

Page 10: ...panel more or less as shown in the figure and hold it in position for a few seconds until it beeps The app will launch automatically and the parameters will be loaded and displayed The access to the...

Page 11: ...If voltage ramp mode is enabled on the other hand P05 01 OFF since 100 of the voltage is independent of the load the time needed will always be constant P01 05 Same concept as the previous parameter f...

Page 12: ...ing attempts are made as set During the alarm status the display alternates the active alarm and the time remaining to the automatic reset P04 07 Delay between successive automatic reset attempts P04...

Page 13: ...ogrammed under the previous parameter Example If the input function is set to Commands menu execution Cxx and this input must execute the command C 07 then P06 n 02 must be set to value 7 P06 n 03 Con...

Page 14: ...asure of the ADXL must be associated to the limit threshold P10 n 02 If the reference measure is a multichannel internal measure this defines the channel P10 n 03 This defines the limit threshold oper...

Page 15: ...n the criteria defined in P04 06 and P04 07 Inhibit The alarm may be temporarily deactivated by activating a programmable input with the alarm inhibit function No LCD The alarm is normally managed but...

Page 16: ...ables the starting It can be used both as a three wire pulse command or two wire continuous command see connection diagrams 2 STOP Motor stop When opened stops the motor either immediately or with a r...

Page 17: ...C06 LIMITS RESET ADVANCED Resets LIM variables with memory C11 REPEAT AUTO SET USER Repeats the AUTOSET wizard C12 SETUP TO DEFAULT USER Restores the factory default settings C13 BACKUP SETUP ADVANCED...

Page 18: ...wire starting 2 T1 1 L1 4 T2 6 T3 3 L2 5 L3 A1 FU1 QF1 PROG OUT A2 A1 QS2 11 14 12 21 24 34 FAN FAN C IN1 IN2 IN3 PROG IN KM1 A B RS485 OUT1 OUT2 OUT3 2 KM1 KM2 KM2 KM1 SB4 SB2 KM2 KM1 OUT2 KM2 SB2 SB...

Page 19: ...I456 GB I 04 17 19 G B MECHANICAL DIMENSIONS ADXL 0030 600 ADXL 0045 600 ADXL 0060 600 ADXL 0135 600 ADXL 0162 600 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 ADXL 0075 600 ADXL 0085 600 ADXL 0115 600...

Page 20: ...I456 GB I 04 17 20 G B 2 T1 4 T2 6 T3 1 L1 3 L2 5 L3 ADXL 0195 600 ADXL 0250 600 ADXL 0320 600...

Page 21: ...2 21 24 34 C IN1 IN2 IN3 FAN NOTE The terminals FAN for the connection of the optional fan code EXP8004 are present only on soft starters ADXL 0030 600 ADXL 0115 600 Soft starters ADXL 0135 600 ADXL 0...

Page 22: ...0115 600 10 600 125 ADXL 0135 600 18 600 150 ADXL 0162 600 18 600 175 ADXL 0195 600 18 600 200 ADXL 0250 600 18 600 250 ADXL 0320 600 18 600 350 NOTE FOR UL ADXL is suitable for use on a circuit of d...

Page 23: ...0195 600 ADXL 0250 600 ADXL 0320 600 12730g Type approvals and conformity Type approvals obtained cULus and EAC for all sizes RCM for ADXL 0030 600 ADXL 0115 600 Type approvals pending RCM for ADXL 01...

Page 24: ...hio IEC EN 61010 1 6 12 2 1 Pulire lo strumento con panno morbido non usare prodotti abrasivi detergenti liquidi o solventi INDICE Pagina Descrizione 25 Funzione dei tasti frontali 25 LED frontali 25...

Page 25: ...Autodiagnostica avanzata Interfaccia NFC per programmazione con smartdevice Interfaccia ottica frontale per programmazione e manutenzione Interfaccia RS485 isolata opzionale in slot dedicato con prot...

Page 26: ...esti all utente nell ordine STEP INFORMAZIONE DEFAULT RANGE 1 Lingua da usare sul display ENG ENG ITA FRA SPA POR DEU 2 Corrente nominale del motore 100 taglia ADXL 50 100 taglia ADXL Esempio per ADXL...

Page 27: ...OFF OFF Nella tabella sottostante sono riportati i parametri caricati automaticamente dalla procedura di AUTOSET nel soft starter ADXL a seconda della tipologia di applicazione e del livello di gravo...

Page 28: ...XC RDU1 in grado di controllare fino a 32 soft starters serie ADXL in contemporanea La distanza massima tra EXC RDU1 e l avviatore pi lontano pu raggiungere i 600mt STATO DISPLAY DESCRIZIONE Mancanza...

Page 29: ...mpre la funzione di limitazione della corrente massima di avviamento Limite di corrente P01 02 Se la corrente erogata sulla pi alta fra le tre fasi raggiunge o supera il limite massimo impostato ADXL...

Page 30: ...che in assenza della alimentazione ausiliaria della scheda di controllo PROTEZIONE TERMICA MOTORE MEDIANTE PTC ADXL dispone dell ingresso IN3 impostabile per la connessione di un sensore di protezione...

Page 31: ...alcun tasto Con il tasto STOP si abbandona l impostazione password LISTA EVENTI ADXL memorizza una lista degli ultimi 60 eventi che viene mantenuta anche in assenza della tensione di alimentazione Ven...

Page 32: ...definire un massimo di 4 allarmi utente liberamente programmabili UA1 UA4 Per ciascun allarme possibile configurare la sorgente cio la condizione che genera l allarme il testo del messaggio che deve...

Page 33: ...ne sullo store online Appoggiando lo smart device sul frontale del ADXL grossomodo nella posizione indicata dalla immagine a lato e tenendolo in posizione per pochi secondi si udir un beep La APP sar...

Page 34: ...dipendente dal carico il tempo necessario sar sempre costante P01 05 Stesso concetto del precedente parametro riferito alla rampa di decelerazione P01 06 Gradino finale di decelerazione Quando la ramp...

Page 35: ...t e conseguenti avviamenti motore pari a quello impostato Durante lo stato di allarme il display mostra alternativamente l allarme in essere e il tempo che manca al comando di reset automatico P04 07...

Page 36: ...unzione programmata al parametro precedente Esempio se la funzione dell ingresso impostata su COMANDO esecuzione del comando Cxx e si vuole far si che questo ingresso esegua il comando C 07 del menu c...

Page 37: ...ie limite LIM1 4 P10 n 01 Definisce a quale delle misure fornite dal ADXL deve essere associata la soglia limite P10 n 02 Se la misura di riferimento una misura interna multicanale qui si definisce qu...

Page 38: ...e pu essere resettato automaticamente secondo il criterio definito dai parametri P04 06 e P04 07 Inibizione L allarme pu essere disabilitato temporaneamente tramite l attivazione di un ingresso progra...

Page 39: ...o un ingresso programmabile deve avere questa funzione Quando chiuso da il consenso all avviamento Pu essere utilizzato sia con comando impulsivo a tre fili sia con comando continuo a due fili vedere...

Page 40: ...cedura guidata wizard AUTOSET C12 SETUP A DEFAULT UTENTE Mette setup a default di fabbrica C13 SALVA COPIA SETUP AVANZATO Salva una copia dei parametri di setup C14 RIPRISTINA SETUP AVANZATO Ripristin...

Page 41: ...viamento a 2 fili 2 T1 1 L1 4 T2 6 T3 3 L2 5 L3 A1 FU1 QF1 PROG OUT A2 A1 QS2 11 14 12 21 24 34 FAN FAN C IN1 IN2 IN3 PROG IN KM1 A B RS485 OUT1 OUT2 OUT3 2 KM1 KM2 KM2 KM1 SB4 SB2 KM2 KM1 OUT2 KM2 SB...

Page 42: ...I456 GB I 04 17 42 I DIMENSIONI MECCANICHE ADXL 0030 600 ADXL 0045 600 ADXL 0060 600 ADXL 0135 600 ADXL 0162 600 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 ADXL 0075 600 ADXL 0085 600 ADXL 0115 600...

Page 43: ...I456 GB I 04 17 43 I 2 T1 4 T2 6 T3 1 L1 3 L2 5 L3 ADXL 0195 600 ADXL 0250 600 ADXL 0320 600...

Page 44: ...12 21 24 34 C IN1 IN2 IN3 FAN NOTA I morsetti FAN per la connessione della ventola opzionale cod EXP80 04 sono presenti solamente su soft starters ADXL 0030 600 ADXL 0115 600 I soft starters ADXL 0135...

Page 45: ...0135 600 18 600 150 ADXL 0162 600 18 600 175 ADXL 0195 600 18 600 200 ADXL 0250 600 18 600 250 ADXL 0320 600 18 600 350 NOTA PER UL ADXL adatto per l utilizzo in un circuito in grado di fornire non pi...

Page 46: ...g Omologazioni e conformit Omologazioni ottenute cULus e EAC per tutte le taglie RCM per ADXL 0030 600 ADXL 0115 600 Omologazioni in corso RCM per ADXL 0135 600 ADXL 0320 600 Conformit a norme IEC EN...

Reviews: