![Lorentz PS1200 Instructions For Installation Operation Service Download Page 28](http://html1.mh-extra.com/html/lorentz/ps1200/ps1200_instructions-for-installation-operation-service_1939703028.webp)
28
LORENTZ PS-XXX Pump Systems
are
excellent for automatic water pressurizing
when powered by a battery system. If you are
raising water vertically AND pressurizing, the
pump must handle to total head. Note the
relationship: 2.31 ft. = 1 PSI (1 Bar = 10
vertical meters.) Example: A pump that lifts
100 vertical feet (30m) and pressurizes to 60
PSI (4 bar) must pump the equivalent of 240
feet (70m). Be sure your
pump
was chosen
correctly for your application. The installation
is similar to that of a conventional AC pump.
A typical pressurizing control assembly is
illustrated in the following photo. These are
standard components, same as used for
conventional AC water pressure systems. The
parts (from left to right) are:
1. check valve (prevents back-flow)
2. pressure gauge 0-100 PSI (0-7 bar)
3. pressure relief valve 75 PSI (5.3 bar)
4. tank tee (a bronze casting that holds all the
components)
5. pressure switch (turns the pump on/off
according to pressure set-points, adjustable)
6. hose outlet (to drain the system or to
supply water when outlet is shut off)
7. ball valve (to shut off the supply to the
outlets)
The components can be purchased from local
suppliers, or as a kit from your pump sup-
plier
WARNING A
PRESSURE
RELIEF VALVE
IS REQUIRED. If
the pressure
switch fails, this
will prevent
extreme pres-
sure from
bursting the tank
or piping and
causing a flood.
Install the valve
near the pressure
tank, before the
shutoff valve. Use
a 1/2" (or larger)
valve set about
25-75% higher
than the cut-out
pressure. Run a
pipe or hose from
its outlet to a
drain or to the
outdoors where
water discharge
will not cause
damage.
5.12 Pressurizing Systems
Pressure tank
A pressure tank is required.
We recommend a captive-air pressure tank
of 40 GALLONS (150 liters) OR MORE, to
assure a steady supply of water pressure as
the pump cycles on and off and the water
demand varies. A large tank is always best.
Size and cost are the only practical limita-
tions. More than one tank can be used to
increase the total capacity.
How to pre-charge a captive-air pressure
tank for PS-XXX Pump Systems
For the system to function properly, the air
bladder in the tank must be pre-charged with
air according to these instructions.
1. Make note of the cut-in setting of the
pressure switch (either by observation or
knowing the factory setting).
2. Turn off the pump and exhaust the water
from the tank if necessary, so the water
pressure is 0.
3. Find the air fitting on top of the tank.
Measure the air pressure in the tank using a
tire gauge.
4. Adjust the pressure to about 3 PSI (.2 bar)
LESS THAN THE CUT-IN PRESSURE.
Pressure switch
PS-XXX Pumps Systems
can use an ordinary pressure switch sold for
conventional AC pumps.
Do not use a
pressure switch with “low water cutout” or
“loss of prime” feature
(with a shutoff lever
ball valve
WATER IN
from pump
pressure switch
To Pressure
Tank
pressure gauge
check valve
tank tee
hose outlet
WATER OUT
to distribution
system