1 3
1 4
Pump is equipped with output por t in order to monitor the status of pump. It
adopts DB9 male socket as output por t (see as below). External control output
star t/stop output, CW/CCCW output and pulse output ( 0 - 100 rpm
corresponding to 0 - 10 kHz). Output signal adopts optoelectronic isolation
circuit. A pull-up resistor and power supply must be added when using.
Terminals Definition
External Control Output
External Control Output Por t Terminal Drawing: DB9
Footswitch Function
Connect
to
to control Star t/Stop of
pump.
Footswitch
External Control Input Port
Terminals Definition
0 - 5 V , 0 - 10 V 4 - 20 mA
Analog input to control the speed
,
CC/CCW Signal
Star t/Stop Signal
1
4
3
4
2
0 5V, 0 10V, 4 20mA
External Control Input Module Connection Diagram
-
-
-
Pulse Signal Input Function:
0 - 10 kHz pulse input
+
-
4
5
CC/CCW Signal
Star t/Stop Signal
+
-
3
1
+
-
2
C O M 1
C O M
0 - 10 kHz Pulse Signal Input Connection Diagram
Analog input in 4 20 mA, 0 - 5 V, 0 10 V external control module
to control the speed of pump.
External control star t/stop input. Open, the pump runs; Close, the
pump stops.
External control direction input. Open, the pump runs clockwise;
Close, the pumps runs counter clockwise.
COM of external control input.
-
-
Terminal 1
Terminal 2
Terminal 3
Terminal 4
COM of external control input
External control star t/stop input. Open, the pump runs; Close, the
pump stops.
External control direction input. Open, the pump runs clockwise;
Close, the pumps runs counter clockwise.
Pulse input in 0
10 kHz pulse external control module to control
the speed of the pump.
COM of pulse input
-
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 1
Terminal 2
Terminal 8
Terminal 4, 6, 7
Star t/Stop output. Pump outputs low level when it runs; pump
output high level when it stops.
CW/CCW output. Pump output low level when it runs clock
wise; pump output high level when it runs count clock wise.
Pulse output, 0 100 rpm corresponding to 0 10 kHz.
COM
-
-
Terminal 13
Terminal 5, 11
Note:
Footswitch is optional accessories. It can only control the star t and stop of the
pump. The speed and direction of the pump are controlled by membrane keypad
and knob on the operation penal.
Star t/Stop control. Close or input
pulse, the pump stops; Open or
input pulse again, the pump runs
COM when connecting terminal 5
and 11 together.
Connection Diagram for Footswitch
External Control Por t
Relay
BT100-1F OPERATING MANUAL
BT100-1F OPERATING MANUAL