Signal Filtering / Averaging
You can adjust the filtering time constant to reduce the effect of noise or instability on your
input signal.
A larger FIL value will give a more stable display, but the response to signal changes will be
slower.
Because your output options, such as analogue output, alarm relays and serial output are all
derived from the displayed value, they will respond at the same rate as the filtered display.
Lockout Switch must be OFF
Press 3 seconds
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Display shows
FIL
.XX.X
where
XX.X
is the time constant in seconds.
Use the UP or DOWN button to
increase or decrease this value
(Default =
FIl. 00.0
)
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
1
2
3
4
Done!
See also Filter Jump setting in the Advanced Menu, if your signal is particularly noisy and
you cannot get sufficient smoothing with this filter.
This feature is available in Easy and Advanced Modes
OFF
Circuit board ON
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Display shows
HFI.
X
where
X
is
the amount of basic filtering.
A
=Low
b
=Medium
C
=High
d
=Most
(Default =
HFI.C
)
Select, then press OK to accept
Select, then press OK to accept