Meter Calibration Modes
You can choose from two main calibration methods.
1. Direct Calibration
- this is when you connect the meter to your system and
make the meter read what you want it to, at 2 different points.
This is the preferred
calibration method, because it allows you to calibrate the system as a whole.
2. Theoretical Calibration
- this is when you type in the sensor’s theoretical
signal level at the bottom and top of itsrange and then type in the value the
display should show, for each signal level.
How to choose a calibration method:-
Lockout Switch must be OFF
Press 3 seconds
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to select dirECt or thEor
Display shows
CAL Src
then
dIreCt
or
thEor
(Default)
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
If you chose Theoretical, you will now be asked whether your input signal
will be DC Current or DC voltage ... the display will show
Input
followed
by
dC A
or
dC V
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to select dc A or dc V
Display shows
Input
then
dC A
for current or
dC V
for voltage
(Default)
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
1
2
3
4
5
Done!
This feature is available in Easy and Advanced Modes