30
Lo Alarm relay action, no hysteresis
Alarm tripped
Alarm reset
Alarm = Lo
Setpoint = 43
Hysteresis = 30
30 Hyst value
Alarm = Lo
Setpoint = 43
Hysteresis = 0
Alarm tripped
Alarm reset
Set.Pt Value
Set.Pt Value
Lo Alarm relay action with Hysteresis
The alarm relay will activate when the measured value is at or below the setpoint value.
The alarm relay will reset whe you rise above the setpoint value
The alarm relay will activate when the measured value is at or below the setpoint value.
The alarm relay will reset whe you rise above the setpoint value by the hysteresis amount
LO
Set..p
Hyst
Mode Setpoint value Hysteresis = 0
LO
Set..p
Hyst
Mode Setpoint value Hysteresis