2
If the train had not reached the WN sensor within 35 seconds of clearing the WF sensor then the
Grade Crossing Pro/2
will
assume the train has reversed. This “timeout” will cause the “action” to shut off as previously described above. Similar
behavior exists for a westbound train with respect to sensors EF, EN and WN (shut off occurs after the last car clears the WN
sensor). The WF and EF sensors may be located as far away from the crossing as you would like. If you are installing gates
then putting these farther out will give the gates enough time to lower before the train reaches the crossing. An HO scale
train running a scale 40 MPH would cover 12 inches in about 1.5 seconds. You will likely choose to have your gates lower in
approximately 4 seconds. So, that would suggest that you should locate WF and EF around 36 inches from the crossing;
consider more distance if you’re running faster trains or less distance if you’re running slower trains! If you are NOT
installing gates then you can choose to place WF and EF wherever convenient and whatever amount of advance notice you
want to give your scale motorists before the train reaches the crossing!
You should make all of the connections to the
Grade Crossing Pro/2
before applying power to it. You can mount the
Grade
Crossing Pro/2
anywhere it is convenient underneath your layout using the four mounting holes provided. The holes will
accept #4 screws; do not enlarge the holes as damage to the circuit board can result and your warranty will be voided!
The
Grade Crossing Pro/2
board has a set of 9 configuration switches on it. Each switch is briefly described below with
more details later in these instructions.
Switch Name
Meaning when OFF/OPEN
Meaning when ON/CLOSED
SETUP
GCP/2 is in normal operating mode
GCP/2 is in sensor setup mode
TRUE LAMP2
Signals don’t fade on/off (like modern signals)
Signals fade on and off (like older signals)
SEN TYPE
Sensors are photocells or external current
detectors
Sensors are infrared
SEN POL
See text in the Sensor Modes section
See text in the Sensor Modes section
FLASH RATE
Normal flashing rate
Fast (2X) flashing rate (see page 3)
GATES USED
Crossing gates are NOT used
Crossing gates are used
GATE DELAY
Signals flash for ~3 seconds before gates lower
Signals flash for ~1.5 seconds before gates lower
BELL MODE
The bell rings continuously while the signals
are flashing
The bell rings only when the gates are moving up
or down (must also have GATES USED ON)
BELL SHUTOFF
The bell shuts off when the flashing stops
See text in the Bell section
Wiring Tomar’s LED-based crossing signals
Tomar’s LED-based crossing signals are pre-wired in a common anode (positive) manner. Since these are dual-sided signals
(i.e. LEDs on both sides of each signal mast) there are 2 yellow and 2 red wires (one from each LED’s cathode) and one
common white wire. Figure 1 below shows you how to wire ONE signal. The
Grade Crossing Pro/2
will support two dual-
sided signals; if you are using two signals then simply replicate the wiring shown for the second signal. Note that EACH
LED connection requires a current limiting resistor. The value of the resistor is dependent upon the voltage applied to the
GCP. You can use Table 1 to determine the MINIMUM resistor value. You can always substitute a ½ watt resistor for a ¼
watt resistor. You can always use a higher value resistor (i.e. more OHMS!) if your signals are too bright to your liking.
Co
m
m
on
(w
hi
te
)
Left Front (yellow)
Left Rear (yellow)
Right Front (red)
Right Rear (red)
Figure 1 – Wiring Tomar’s LED-based signals
Voltage supplied to
GCP/2
Minimum Resistor
Value
9V DC
390 ohm, 1/4W
12V DC
470 ohm, 1/4W
14V DC
680 ohm 1/4W
7V AC
390 ohm, 1/4W
9V AC
560 ohm, 1/4W
12V AC
1K ohm, 1/4W
16V AC
1.2K ohm, 1/4W
Table 1 – Current limiting resistors