10
11.2
Door Settings
Relay Output Delay Time
To set door relay strike time
*
Master code
#
4 0
~
99 #
*
0-99 is to set the door relay time 0-99 seconds
Door Open Detection
Door Open Too Long (DOTL) warning
. When used with an optional magnetic contact or built-in
magnetic contact of the lock, if the door is opened normally, but not closed after 1 minute, the inside
buzzer will beep automatically to remind people to close the door and continue for 1 minute before
switching off automatically.
Door Forced Open warning.
When used with an optional magnetic contact or built-in magnetic contact
of the lock, if the door is forced open, or if the door is opened after 20 seconds ,the inside buzzer and
alarm output will both operate. The Alarm Output time is adjustable between 0-3 minutes with the
default being 1 minute.
To disable door open detection. (Factory
default)
6 0 #
To enable door open detection
6 1 #
Alarm output time
To set the alarm output time (0-3 minutes)
Factory default is 1 minute
5 0
~
3 #
Keypad Lockout & Alarm Output options
.
If there are 10 invalid cards or 10 incorrect PIN numbers
in a 10 minute period either the keypad will lockout for 10 minutes or both the alarm and the inside
buzzer will operate for 10 minutes, depending on the option selected below.
Normal status: No keypad lockout or
alarm (factory default)
7 0 # (Factory default setting)
Keypad Lockout
7 1 #
Alarm and inside buzzer operate
7 2 #
To remove the alarm
To reset the Door Forced Open warning
Read valid card
or
Master Code #
To reset the Door Open Too Long warning Close the door
or
Read valid card
or
Master Code #