background image

6

3  

Technology, installation and commissioning

Clamp ring screw connections

■ 

Cut the copper pipe to length and deburr.

■ 

First, slide the clamp ring nut over the pipe, then slide the 

   clamp ring. 

■ 

Insert the prepared pipe into the screw connection until its 

   stop is reached. 

■ 

Tighten clamp ring nut by hand.

■ 

Use open-ended wrench to tighten clamp ring screw 

     connection (approx. 33 Ft lb),  re-tighten if necessary.

■ 

When tightening the clamp ring screw connection, use two 

    wrenches

using one wrench to prevent the pumping station 

    from turning.

Flat seal screw connections

■ 

All pre-fitted solar station screw connections are firmly 

   tightened in the factory so that they do not need to be 
     retightened. 

Torque levels when tightening flat seal screw connections 
using AFM 34 flat seals, s = 2mm.

 

– 

3/4" screw connection 26 Ft. lb

 

 1" screw connection 40 Ft. lb

 

 1 1/4" screw connection 66 Ft. lb

 

 1 1/2" screw connection 96 Ft. lb

Operation, multi-function ball valve and 

check valve

■ 

The forward flow ball valve must be open for filling, flushing 

   and bleeding solar systems with a filling and flushing pump. 
   The return ball valve should be closed.

■ 

Both flow checks should be opened in order to drain the 

    solar system (thermometer handles in 45

°

 position).

■ 

The two mult-function ball valves must be fully open in 

  order to operate the solar system (turn the red and blue 
  thermometer handles counter-clockwise until the stop is 
    reached).

Figure 4-1 Forward flow multi-functioning instruments

 

 

SETTING FOR OPERATIONS, 

FILLING, FLUSHING, DRAINING

 

FLOW CHECK CLOSED

BALL VALVE OPEN 

DRAINING

FLOW CHECK OPEN

BALL VALVE 1/2 OPEN

SERVICE

BALL VALVE 
   CLOSED

Figure 4-2 Return multi-functioning instruments

 

 

SETTING FOR OPERATIONS 

FLOW CHECK CLOSED

BALL VALVE OPEN

 

DRAINING

FLOW CHECK OPEN

 

BALL VALVE 1/2 OPEN

 

SERVICE, FILLING FLUSHING

BALL VALVE CLOSED

 

SL-PS Installation & Operation Manual

Summary of Contents for TISUN PS1000

Page 1: ...only be used by a qualified heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death...

Page 2: ...to personal injury or property damage HAZARD DEFINITIONS 2 1 GENERAL INFORMATION Included components 3 4 2 INSTALLING THE SOLAR STATION Installing the solar station on a wall 5 Installing the relief v...

Page 3: ...operation The provisions stated in DIN EN 12976 1 should be observed when installing solar systems The expansion tank should be regularly checked according to DIN 4807 Solar systems should be grounde...

Page 4: ...with mounting kit Installation kit Wall and tank bracket with mounting kit 1 General Information Solar Control unit LCD Plus solar control unit with integrated energy balance function 2 collector and...

Page 5: ...ion should be noted The safety valve must be easily accessible No valves should be placed between relief valve and pump station The relief valve should be piped to a suitable drain as close as possibl...

Page 6: ...tion 40 Ft lb 1 1 4 screw connection 66 Ft lb 1 1 2 screw connection 96 Ft lb Operation multi function ball valve and check valve The forward flow ball valve must be open for filling flushing and blee...

Page 7: ...erms of freeze protection Fill the solar system via the filling and flushing pump and then flush the solar circuit for at least 15 min to purge all of the air out of the circuit Close the fill flush v...

Page 8: ...4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 Volumetric flow rate GPM Residual delivery height Ft Max residual delivery height pressure drop of components Solar group with Grundfos UP 25 120U pump and GF Sens...

Page 9: ...Assignment of measurement range 32 212 F is equal to 0 5 3 5V Temperature rate calculation T 32 F U 0 5 V 3V 180 F Figure 6 4 VFS 2 40 temperature output signal VFS 2 40 output signal temperature Assi...

Page 10: ...size DN20 Measuringrange 26 3 17 GPM 5 10 5 GPM Measuring range 5 10 5 GPM Output signal Q 0 5 to 3 5 V proportional to GPM Output signal T 0 5 to 3 5 V proportional to 32 212 F Max pressure 145 psi...

Page 11: ...FLAT SEALS FOR PUMP Size 30 x 22 x 2 1 Size 44 5 x 33 x 2 1 1 2 Material AFM 34 light grey Long term temperature Liquid 482 F water vapor 360 F Peak temp briefly 720 F FLAT SEAL FOR SAFETY GROUP Size...

Page 12: ...0 UPS 25 99U 1 1 2 180 F12K09 115V 60Hz 13 Solar control unit LCD plus USA 115 Volt w SD card 14 SPS0250 Sensor direct 0 26 3 17 gpm w cable SPS0500 Sensor direct 0 50 10 5 gpm w cable 15 Power cord U...

Page 13: ...16 Solar cross piece cpl USA w reducing pc and cap 17 Flow sensor housing 0 50 10 5 gpm w fill flush valve USA 18 Safety group KS0150 USA 19 Solar control unit LCD plus USA 115 Volt w SD card 20 UP 2...

Page 14: ...x 33 Ft lb When tightening the clamp ring screw connection use two wrenches one wrench to prevent the pumping station from turning Disassembling the solar station Wall bracket for repairs and service...

Page 15: ...atures and system pressures Allow pump to cool first Fully unscrew bleed screw and check ease of movement of pump rotor by turning the slotted shaft end with a screwdriver use force to turn if necessa...

Page 16: ...Revision Notes Revision A ECO C06520 initial release Revision B ECO C07610 reflects formatting adjustments SL PS I O Rev B 3 11...

Reviews: