background image

        

Installation & Operation Manual

6

Multiple tank connections (boiler side)

Multiple tank installations must be done in the “reverse-return” 
manner.  The reason for this is to create the same pressure drop 
(and therefore, the same flow) through the coil of each tank.  
The boiler manifold piping must be sized so that each coil has 
the flow rate called for in Table 3B.  

Because the pressure drop through tank coils varies from size 
to size, it is hard to predict the flow rate that will be developed 
through each coil when two tanks of different sizes are placed in 
the same manifold.  For this reason it is best not to mix tanks of 
different sizes in the same zone if their recovery is critical.

Table 3B

Pressure Drop Values

MODEL

WATER

INLET

(NPT) 

WATER

OUTLET

(NPT) 

COIL 

CONNECTION

(NPT)  

COIL 

LENGTH

(FT)  

SQ FT 

SURFACE

AREA 

PRESSURE DROP

(FT/HD)

GPM

8

 GPM

12 

GPM

16

GPM

20 

GPM

SIT030

1

1

1

24

8.0

.36

.91

2.06

3.66

5.71

SIT040

1

1

1

30.8

10.0

.41

1.04

2.34

4.16

6.49

SIT050

1

1

1

36.5

12.0

.46

1.18

2.67

4.74

7.4

SIT065

1.5

1.5

1

41.5

13.5

.61

1.57

3.53

6.27

9.8

SIT080

1.5

1.5

1

41.5

13.5

.61

1.57

3.53

6.27

9.8

SIT119

1.5

1.5

1

67.3

22.0

.73

1.87

4.22

7.5

11.71

3  

Boiler side piping 

Figures 3-1 thru 3-4 show typical boiler side piping for 
several common situations.  Regardless of which system is 
used it is imperative that the flow rates called for in Table 
3B are developed through the coil.  This requires properly 
sized piping and a properly sized pump.  

The system shown in FIG’s 3-1 thru 3-4 are described 
below:

Zone with circulator to Aquastat

This system is like the circulator zone system on a straight 
heat job except that one of the zones goes to the tank 
instead of radiation.  As on any circulator zone system 
check valves should be installed in each zone to prevent 
unwanted circulation through zones which are not calling 
for heat.  Figure 3-1 on page 7 illustrates typical circulator 
zone piping.

Zone with valve to Aquastat

As with the circulator zone system, this system is just like a 
standard heating zone system except that one of the zones 
is connected to the tank coil as shown in FIG. 3-2.  The 
system circulator must be large enough to move boiler 
water through the coil regardless of the flow rate required 
through the heating zones.

DHW prioritization

This piping system is designed to provide direct hot 
water priority over the other zones in the heating system.  
When there is a Domestic Hot Water (DHW) call for 
heat, the Knight control will shut off the boiler circulator 
and activate the domestic hot water circulator.  Once the 
DHW demand is satisfied, the boiler circulator will be 
readjusted as demand requires.  The circulator must be 
large enough to move the boiler water through the coils.  
The recommended piping for a DHW priority system is 
depicted in FIG. 3-3 on page 9.

Table 3A

Pressure Drop Chart

SIT119,

12.00

SIT030 - 119 FRICTION LOSS 

SIT030

SIT040

SIT050

SIT065

 

&

 

080,

SIT119,

0.00

2.00

4.00

6.00

8.00

10.00

12.00

5

8

12

16

20

FO

O

T

 

HE

A

D

SIT030 - 119 FRICTION LOSS 

GPM

Summary of Contents for SQUIRE SIT030

Page 1: ...d result in severe personal injury death or substantial property damage WARNING Save this manual for future reference SIT I O Rev H CAUTION The heat transfer medium must be water or other nontoxic flu...

Page 2: ...EFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Single Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING Zone with Circulator...

Page 3: ...AS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc...

Page 4: ...PT SEE NOTE 1 2 SIT030 SIT119 PART NO A in B in C in D in E in F in SIT030 SIT040 SIT050 SIT065 SIT080 SIT119 3 1 16 3 1 16 3 5 8 3 5 16 3 5 16 3 5 16 8 3 16 8 3 16 9 1 8 9 1 8 9 1 8 9 3 8 21 3 4 25 1...

Page 5: ...or appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on...

Page 6: ...s properly sized piping and a properly sized pump The system shown in FIG s 3 1 thru 3 4 are described below Zone with circulator to Aquastat This system is like the circulator zone system on a straig...

Page 7: ...EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE DRAIN ZONE 1 ZONE 2 ZONE...

Page 8: ...D SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE DRAI...

Page 9: ...IN POINT TYPICAL MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HO...

Page 10: ...RELIEF VALVE TYPICAL TANK SENSOR AQUASTAT TYPICAL CHECK VALVE SQUIRE SQUIRE BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL MAKE UP WATER FROM...

Page 11: ...reverse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be rem...

Page 12: ...sed with water heaters are also called tempering valves or mixing valves An anti scald valve mixes cold water in with the outgoing hot water to assure that hot water reaching a building fixture is at...

Page 13: ...of piping can reduce discharge capacity directly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the T P relief valve and the tank connection or...

Page 14: ...VALVE SHUT OFF VALVE ANTI SCALD MIXING VALVE DRAIN FIELD SUPPLY RECIRCULATION PUMP TO BOILER FROM BOILER CHECK VALVE TANK SENSOR AQUASTAT SQUIRE Figure 4 2 Recommended Domestic Water Piping Please not...

Page 15: ...sensor has a built in high temperature limit set at 194 F NOTICE The sensor supplied contains an Auto Reset High Limit 194 F 3 The Knight boiler will automatically read the sensor and default the tank...

Page 16: ...ntrol TST20016 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIRECT T...

Page 17: ...xtended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and th...

Page 18: ...s to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve c...

Page 19: ...IT030 27 0 1 1 1 5 160 183 99 000 14 0 3 9 SIT040 40 0 1 6 0 9 181 208 115 000 14 0 4 5 SIT050 51 6 1 7 0 8 209 255 133 000 14 0 5 3 SIT065 67 0 1 9 0 7 263 327 154 000 14 0 5 7 SIT080 81 5 2 1 0 6 26...

Page 20: ...Hour Rating of no less than 165 gallons Fixture Count Guide To quickly estimate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour...

Page 21: ...9574 132764 94115 114116 125111 134044 146207 Boiler Heating Capacity Table 8B First Hour Rating 180 F Boiler Loop Water Knight Boiler First Hour Rating 180 F Boiler Loop Water Knight Boiler SIT065 SI...

Page 22: ...ler Heating Capacity First Hour Rating 180 F Boiler Loop Water Universal Sizing 45 000 295 000 Btu hr Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Out...

Page 23: ...Heating Capacity First Hour Rating 200 F Boiler Loop Water Universal Sizing 45 000 295 000 Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Outlet 115 14...

Page 24: ...for section 3 Boiler Side Piping FIG 3 1 3 4 a new image for section 4 Domestic Side Tank Piping FIG 4 2 and the update of the Pressure Drop chart on page 6 Revision E ECO C06035 reflects the update o...

Reviews: