Installation & Operation Manual

13

 NOTICE

Verify that the combination 
temperature and pressure relief valve 
complies with local codes.  If the 
combination temperature and pressure 
relief valve does not comply with local 
codes, replace it with one that does.  
Follow the installation instructions in 
this section.

 NOTICE

The Lochinvar SIT series water heaters 
will absorb/store less than 200,000 Btu/
hr when domestic water outlet 
temperature is 210°F and boiler water 
supply temperature is 240°F. Listed 
outputs are based on ASME Section VIII 
Interpretation VIII-1-86-136. Check 
with local codes for applicability.

Standard installation

• 

Install the T&P relief valve in the connection marked 

 “Relief 

Valve”.

T&P relief valve discharge piping

 

T&P relief valve discharge piping 

MUST

 be:

 

 

- made of material serviceable for a temperature of 

 

 

   250°F or greater.

 

 

- directed so that hot water flows away from all persons.

 

 

- directed to a suitable place for disposal.

 

 

- installed so as to allow complete draining of the T&P 

 

 

   relief valve and discharge line.

 

 

- terminated within 6" of the floor.

 

T&P relief valve discharge piping 

MUST NOT

 be:

 

 

- excessively long.  Using more than two (2) elbows or 

 

 

   15 feet of piping can reduce discharge capacity.

 

 

- directly connected to a drain.  Refer to local codes.

 

 

- subject to freezing.

 WARNING

Do not install any valve between the T&P 
relief valve and the tank connection or 
on the T&P relief valve discharge piping.  
Improper placement and piping of T&P 
relief valve can cause severe personal injury, 
death or substantial property damage.

 CAUTION

The T&P relief valve is not intended for 
constant duty, such as relief of pressure 
due to repeated normal system expansion.  
Correct this condition by installing a 
properly sized expansion tank in a domestic 
water system.  Refer to the expansion tank 
manufacturer’s installation instructions for 
proper sizing.

4  

Domestic side (tank) piping 

(continued)

 

Do not place a valve between the combination T&P relief 
valve and the tank.

 WARNING

Failure to install and maintain a new, listed 
3/4" X 3/4" T&P relief valve will release 
the manufacturer from any claim which 
might result from excessive temperature 
and pressures.

Determine T&P relief valve size by the following 
specifications, unless they conflict with local codes:
 
 

SIT030/040/050 - 3/4" NPT with a minimum CSA 

 

 

Rating of 105,000 Btu/hr.

 

SIT065/080/119 - 3/4" NPT with a minimum CSA 

 

 

Rating of 200,000 Btu/hr.

Table 4A

Minimum Relief Valve (CSA Rating)

Model

Btu/hr

SIT030

105,000

SIT040

105,000

SIT050

105,000

SIT065

200,000

SIT080

200,000

SIT119

200,000

Summary of Contents for SQUIRE SIT030

Page 1: ...d result in severe personal injury death or substantial property damage WARNING Save this manual for future reference SIT I O Rev H CAUTION The heat transfer medium must be water or other nontoxic flu...

Page 2: ...EFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Single Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING Zone with Circulator...

Page 3: ...AS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc...

Page 4: ...PT SEE NOTE 1 2 SIT030 SIT119 PART NO A in B in C in D in E in F in SIT030 SIT040 SIT050 SIT065 SIT080 SIT119 3 1 16 3 1 16 3 5 8 3 5 16 3 5 16 3 5 16 8 3 16 8 3 16 9 1 8 9 1 8 9 1 8 9 3 8 21 3 4 25 1...

Page 5: ...or appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on...

Page 6: ...s properly sized piping and a properly sized pump The system shown in FIG s 3 1 thru 3 4 are described below Zone with circulator to Aquastat This system is like the circulator zone system on a straig...

Page 7: ...EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE DRAIN ZONE 1 ZONE 2 ZONE...

Page 8: ...D SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE DRAI...

Page 9: ...IN POINT TYPICAL MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HO...

Page 10: ...RELIEF VALVE TYPICAL TANK SENSOR AQUASTAT TYPICAL CHECK VALVE SQUIRE SQUIRE BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL MAKE UP WATER FROM...

Page 11: ...reverse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be rem...

Page 12: ...sed with water heaters are also called tempering valves or mixing valves An anti scald valve mixes cold water in with the outgoing hot water to assure that hot water reaching a building fixture is at...

Page 13: ...of piping can reduce discharge capacity directly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the T P relief valve and the tank connection or...

Page 14: ...VALVE SHUT OFF VALVE ANTI SCALD MIXING VALVE DRAIN FIELD SUPPLY RECIRCULATION PUMP TO BOILER FROM BOILER CHECK VALVE TANK SENSOR AQUASTAT SQUIRE Figure 4 2 Recommended Domestic Water Piping Please not...

Page 15: ...sensor has a built in high temperature limit set at 194 F NOTICE The sensor supplied contains an Auto Reset High Limit 194 F 3 The Knight boiler will automatically read the sensor and default the tank...

Page 16: ...ntrol TST20016 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIRECT T...

Page 17: ...xtended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and th...

Page 18: ...s to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve c...

Page 19: ...IT030 27 0 1 1 1 5 160 183 99 000 14 0 3 9 SIT040 40 0 1 6 0 9 181 208 115 000 14 0 4 5 SIT050 51 6 1 7 0 8 209 255 133 000 14 0 5 3 SIT065 67 0 1 9 0 7 263 327 154 000 14 0 5 7 SIT080 81 5 2 1 0 6 26...

Page 20: ...Hour Rating of no less than 165 gallons Fixture Count Guide To quickly estimate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour...

Page 21: ...9574 132764 94115 114116 125111 134044 146207 Boiler Heating Capacity Table 8B First Hour Rating 180 F Boiler Loop Water Knight Boiler First Hour Rating 180 F Boiler Loop Water Knight Boiler SIT065 SI...

Page 22: ...ler Heating Capacity First Hour Rating 180 F Boiler Loop Water Universal Sizing 45 000 295 000 Btu hr Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Out...

Page 23: ...Heating Capacity First Hour Rating 200 F Boiler Loop Water Universal Sizing 45 000 295 000 Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Outlet 115 14...

Page 24: ...for section 3 Boiler Side Piping FIG 3 1 3 4 a new image for section 4 Domestic Side Tank Piping FIG 4 2 and the update of the Pressure Drop chart on page 6 Revision E ECO C06035 reflects the update o...

Reviews: