12

        

Installation & Operation Manual

4  

Domestic side (tank) piping

Temperature & pressure (T&P) relief valve

For protection against excessive 
temperatures 

and pressure, install 

temperature and pressure protective 
equipment required by local codes. 
This equipment shall not be less than a 
combination temperature and pressure relief 
valve certified by a nationally recognized 
testing laboratory that maintains periodic 
inspection of production of listed equipment 
or materials as meeting the requirements for 
Relief Valves and Automatic Gas Shutoff 
Devices for Hot Water Supply Systems, 
ANSI Z21.22 and the Standard CAN1-4.4, 
Temperature, Pressure, Temperature and 
Pressure Relief Valves and Vacuum Relief 
Valves. The combination temperature and 
pressure relief valve shall be marked with 
a maximum set pressure not to exceed the 
maximum working pressure of the water 
heater. The combination temperature and 
pressure relief valve shall also have an hourly 
rated temperature steam BTU discharge 
capacity not less than shown in Table 4A.

Install the combination temperature and 
pressure relief valve into the opening 
provided and marked for this purpose on 
the water heater.

 WARNING

Anti-scald valves (mixing valves)

Anti-scald valves used with water heaters are also called 
tempering valves or mixing valves. An anti-scald valve 
mixes cold water in with the outgoing hot water to assure 
that hot water reaching a building fixture is at a temperature 
low enough to be safe. ASSE1017  and ASSE1070 certified 
valves are recommended.

Usually, the maximum temperature of the outlet water will 
stay near the setting of the tank control.  In some cases, 
however, hot water usage patterns can cause the outlet 
water temperature to rise significantly above the control 
setting.

The temperature of water going to the fixtures may be 
more carefully controlled through the use of a thermostatic 
mixing valve.  This device blends a controlled amount of 
cold water with the hot water leaving the tank so that water 
at a more constant temperature exits the mixing valve. 

 

Anti-scald mixing valve piping is illustrated in FIG.’s 3-1 
thru 3-4.

Install drain valve

Drain valve and fittings are supplied by others.

Standard Installation

 

• 

Install a tee connection at the domestic cold water 

  inlet 

(FIG. 

4-1).

DRAIN

VALVE

Figure 4-1 Drain Valve Installed

 WARNING

An anti-scald mixing valve does not 
eliminate the risk of scalding.

*  Set the tank thermostat as low as 
 practical.

*  Feel water before bathing or 
 showering.

If anti-scald or anti-chill protection 

 

is required, use devices specifically 

 

designed for such service. Install 

 

these devices in accordance with 

 

their manufacturer’s instructions.

Summary of Contents for SQUIRE SIT030

Page 1: ...d result in severe personal injury death or substantial property damage WARNING Save this manual for future reference SIT I O Rev H CAUTION The heat transfer medium must be water or other nontoxic flu...

Page 2: ...EFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Single Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING Zone with Circulator...

Page 3: ...AS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc...

Page 4: ...PT SEE NOTE 1 2 SIT030 SIT119 PART NO A in B in C in D in E in F in SIT030 SIT040 SIT050 SIT065 SIT080 SIT119 3 1 16 3 1 16 3 5 8 3 5 16 3 5 16 3 5 16 8 3 16 8 3 16 9 1 8 9 1 8 9 1 8 9 3 8 21 3 4 25 1...

Page 5: ...or appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on...

Page 6: ...s properly sized piping and a properly sized pump The system shown in FIG s 3 1 thru 3 4 are described below Zone with circulator to Aquastat This system is like the circulator zone system on a straig...

Page 7: ...EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE DRAIN ZONE 1 ZONE 2 ZONE...

Page 8: ...D SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE DRAI...

Page 9: ...IN POINT TYPICAL MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HO...

Page 10: ...RELIEF VALVE TYPICAL TANK SENSOR AQUASTAT TYPICAL CHECK VALVE SQUIRE SQUIRE BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL MAKE UP WATER FROM...

Page 11: ...reverse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be rem...

Page 12: ...sed with water heaters are also called tempering valves or mixing valves An anti scald valve mixes cold water in with the outgoing hot water to assure that hot water reaching a building fixture is at...

Page 13: ...of piping can reduce discharge capacity directly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the T P relief valve and the tank connection or...

Page 14: ...VALVE SHUT OFF VALVE ANTI SCALD MIXING VALVE DRAIN FIELD SUPPLY RECIRCULATION PUMP TO BOILER FROM BOILER CHECK VALVE TANK SENSOR AQUASTAT SQUIRE Figure 4 2 Recommended Domestic Water Piping Please not...

Page 15: ...sensor has a built in high temperature limit set at 194 F NOTICE The sensor supplied contains an Auto Reset High Limit 194 F 3 The Knight boiler will automatically read the sensor and default the tank...

Page 16: ...ntrol TST20016 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIRECT T...

Page 17: ...xtended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and th...

Page 18: ...s to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve c...

Page 19: ...IT030 27 0 1 1 1 5 160 183 99 000 14 0 3 9 SIT040 40 0 1 6 0 9 181 208 115 000 14 0 4 5 SIT050 51 6 1 7 0 8 209 255 133 000 14 0 5 3 SIT065 67 0 1 9 0 7 263 327 154 000 14 0 5 7 SIT080 81 5 2 1 0 6 26...

Page 20: ...Hour Rating of no less than 165 gallons Fixture Count Guide To quickly estimate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour...

Page 21: ...9574 132764 94115 114116 125111 134044 146207 Boiler Heating Capacity Table 8B First Hour Rating 180 F Boiler Loop Water Knight Boiler First Hour Rating 180 F Boiler Loop Water Knight Boiler SIT065 SI...

Page 22: ...ler Heating Capacity First Hour Rating 180 F Boiler Loop Water Universal Sizing 45 000 295 000 Btu hr Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Out...

Page 23: ...Heating Capacity First Hour Rating 200 F Boiler Loop Water Universal Sizing 45 000 295 000 Model SIT065 SIT080 SIT119 Circulator Flow GPM 5 8 12 16 20 5 8 12 16 20 5 8 12 16 20 Domestic Outlet 115 14...

Page 24: ...for section 3 Boiler Side Piping FIG 3 1 3 4 a new image for section 4 Domestic Side Tank Piping FIG 4 2 and the update of the Pressure Drop chart on page 6 Revision E ECO C06035 reflects the update o...

Reviews: