44
13.4
LOW VOLTAGE CONNECTOR STRIP
LOW
VOLTAGE
CONNECTION
STRIP
PIN
CONNECTION
NOTES
1-2
EXTERNAL
CONTROL
These connections should be used to enable the heater via a BMS on/off input.
3-4
SPARE EXTERNAL
CONTROL
This can be used to prevent the unit firing until a fan dilution system or other external control has proved
5-6
24V COM RELAY
Can be used to supply an enable signal to an external control such as a fan dilution system
7-8
RUNTIME
CONTACTS
An internal volt free contact across pins 7 &8 will close in the event of the burner operating. This connection can be used by a BMS
to monitor the operation of the heater.
9-10
ALARM
CONTACTS
An internal volt free contact across pins 9 & 10 will close in the event of the heater locking out. This connection can be used by a
BMS to monitor the operation of the heater.
LOW
VOLTAGE
CONNECTION
TERMINAL
DETAILS