17
Model Number
SHW35-245CE
SHW46-325CE
SHW61-325CE
SHW86-410CE
SHW116-410CE
SHW146-410CE
FLUE DATA TYPE B
23
Nominal flue diameter (d
nom
)
mm
80
100
Nominal flue diameter (d
outside
)
mm
80 +/-0.3
100 +/-0.3
Nominal flue diameter (d
inside
)
mm
81 +/-0.6
101+/-0.6
Nominal flue diameter (L
insert
)
mm
50 +20/ -2
50 +20/ -2
Maximum flue gas temp.
°C
120
Maximum equivalent length
m
60
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
Flue gas temperature
°C
70
Flue draught requirements
mbar
-0.03 to -0.1
FLUE DATA TYPE C
13
& C
33
Nominal flue diameter
mm
80/125
100/150
Maximum flue gas temp.
°C
120
Maximum equivalent length
m
30
13
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
FLUE DATA TYPE C
43
& C
53
Nominal flue diameter (d
nom
)
mm
80
100
Nominal flue diameter (d
outside
)
mm
80 +/-0.3
100 +/-0.3
Nominal flue diameter (d
inside
)
mm
81 +/-0.6
101+/-0.6
Nominal flue diameter (L
insert
)
mm
50 +20/ -2
50 +20/ -2
Minimum flue gas temp
°C
35
Average flue gas temp
°C
70
Maximum flue gas temp.
°C
120
Maximum equivalent length
m
60*
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
FLUE DATA TYPE C
63
Nominal flue diameter (d
nom
)
mm
80
100
Nominal flue diameter (d
outside
)
mm
80 +/-0.3
100 +/-0.3
Nominal flue diameter (d
inside
)
mm
81 +/-0.6
101+/-0.6
Nominal flue diameter (L
insert
)
mm
50 +20/ -2
50 +20/ -2
Minimum flue gas temp
°C
35
Average flue gas temp
°C
70
Maximum flue gas temp.
°C
120
Max combustion air temperature
°C
40
Maximum equivalent length
m
48
FLUE
SYSTEM
TECHNICAL
DATA
TABLE
*
On twin pipe systems, the maximum equivalent length is the sum of the air inlet components and the exhaust components.