22

RELIEF VALVE

At least once a year, the temperature and pressure relief valve 
should be checked to ensure that it is in operating condition.  Lift 
the lever at the top of the valve several times until the valve seats 
properly and operates freely.

If the appliance installation includes other relief valves, such as 
in “remote” storage tanks etc., check their relief valve operation 
with the same frequency.

 WARNING

THE WATER PASSING OUT OF THE VALVE DURING THIS CHECKING 

OPERATION MAY BE EXTREMELY HOT. AVOID CONTACT AND 

DISCHARGE SAFELY TO PREVENT WATER DAMAGE.

If  the  temperature  and  pressure  relief  valve  on  the  heater 

discharges periodically or continuously, a problem exists.  This 

may be due to unusually high water temperatures or pressures 

in the system, or to a faulty relief valve.  Contact your dealer or 

a qualified service technician to find the cause of the problem 

and to correct it.  This may also be due to thermal expansion 

in a closed water supply system.  Contact the water supplier 

or local plumbing inspector on how to correct this situation.  

 

DO NOT PLUG THE TEMPERATURE AND PRESSURE 

RELIEF VALVE.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 

TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL 

VALVE TO THE APPLIANCE.

HOT WATER ODOR

On occasion, hot water may develop a strong odor.  If this occurs 

drain  the  heater  completely,  flush  thoroughly,  and  refill.    If  the 

problem persists, chlorination of the heater and replacement of 

the factory installed magnesium anodes with aluminum anodes 

may correct the condition.

Occasionally water softener companies recommend removal of 

heater anodes for odor reasons.

 CAUTION

Unauthorized removal of the anode(s) will void the warranty.  

For further information contact your dealer.

ANODE ROD INSPECTION

The  heater  tank  is  equipped  with  anode  rods  to  provide 

corrosion control.  At least once a year the anode rods should 

be checked to determine if replacement is necessary.  Initially 

the anode rods are approximately 7/8” in diameter with a 1/8” 

diameter steel core wire running down the center of the anode 

material.  THE ANODES SHOULD BE REPLACED when the 

1/8”  diameter core wire is visible as this means that the  anode 

material has been expended in the control of corrosion.

For models with top inlet and outlet, it is recommended that, 

before  removing  the  inner  cover  for  cleaning,  inspection  or 

removal of inner parts, you obtain two new nipple collars.  The 

nipple  collars  on  the  heater  will  usually  be  damaged  when 

removed.  New pipe collars will insure that the seal is such as 

to prevent leakage of flue products when properly installed.

NOTE:

 

 

Anode  rod  inspection  may  need  to  be  made  more 

frequently in areas subject to acid rain that obtains their water 

supply from surface water as the low pH will accelerate anode 

activity.

CAUTION:

 

 

Close cold water inlet valve serving heater and open 

nearby hot water faucet to relieve the pressure in the heater before 

attempting to remove anode(s) for inspection.

FLUSHING

1.  Turn off the heater electrical disconnect switch.
2.  Open the drain valve and allow water to flow until it runs clean.
3.  Close the drain valve when finished flushing.
4.  Turn on the heater electrical disconnect switch.

DRAINING

The heater must be drained if it is to be shut down and exposed 

to freezing temperatures.  Maintenance and service procedures 

may also require draining the heater.

1.  Turn off the heater electrical disconnect switch.
2.  Close the cold water inlet valve to heater.
3.  Open a nearby hot water faucet to vent the system.
4.  Open the heater drain valve.
5.  If the heater is being drained for an extended shutdown, it is 

suggested the drain valve be left open during this period.

  •  Follow FILLING instructions when restoring hot water service.

RECOMMENDED PROCEDURE FOR PERIODIC 

REMOVAL OF LIME DEPOSITS FROM TANK 

TYPE COMMERCIAL WATER HEATERS

The amount of calcium carbonate (lime) released from water is

in direct proportion to water temperature and usage, see chart. 

The higher the water temperature or water usage, the more lime

deposits are dropped out of the water. This is the lime scale which 

forms in pipes, heaters and on cooking utensils.

Lime accumulation not only reduces the life of equipment but also

reduces efficiency of the heater and increases fuel consumption.

The  usage  of  water  softening  equipment  greatly  reduces  the 

hardness  of  the  water.  However,  this  equipment  does  not 

always remove all of the hardness (lime). For this reason it is 

recommended that a regular schedule for deliming be maintained.

The  time  between  cleaning  will  vary  from  weeks  to  months 

depending upon water conditions and usage. The depth of lime 

buildup should be measured periodically. Heaters equipped with 

cleanouts  will  have  about  2”  of  lime  buildup  when  the  level  of 

lime has reached the bottom of the cleanout opening. A schedule 

for deliming should then be set up,based on the amount of time 

it would take for a 1” buildup of lime. It is recommended that the 

water heater initially be inspected after 6 months.

Example 1:

If initial inspection after 6 months shows 1/2” of lime accumulation.

Therefore, the heater should be delimed once a year.

Summary of Contents for CGL150

Page 1: ...ed in U S A 1011 322880 000 CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for b...

Page 2: ...installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available from the National Fire Protection...

Page 3: ...ater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTIC AND OR EXHAUST FANS OPERATING ON THE PREMISES WITHAWATER HEATER...

Page 4: ...n per cubic foot of air Therefore the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply Failure to make this reduction would result in an...

Page 5: ...DUCER BLOWER ASSEMBLY All units are equipped with a exhaust inducer The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by products int...

Page 6: ...ns above 2000 feet 610m refer to HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure LEVELING If the unit is not level insert the bolts which were used in crating into the...

Page 7: ...ater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heaters This water heater...

Page 8: ...r well Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device...

Page 9: ...ALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIMENT TRAPORDRIPLEG MUSTBEINCORPORATEDINTHEPIPING SEE FIG 9 THE DIRT LEG...

Page 10: ...h the latest version of the National Electrical Code ANSI NFPA No 70 FIGURE 10 SINGLE UNIT WIRING DIAGRAM must conform to all local code authority having jurisdiction AN ELECTRICAL GROUND IS REQUIRED...

Page 11: ...emperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the te...

Page 12: ...LD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Page 13: ...BE CLOSED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Page 14: ...in the installation diagrams on the following pages are typical The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject HEATER WITH...

Page 15: ...NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LI...

Page 16: ...RS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEA...

Page 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN LOCHINVAR T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Page 18: ...rner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or the uni...

Page 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Page 20: ...WHICH INJURYOCCURS VARIES WITH THE PERSON S AGE AND TIME OF EXPOSURE THE SLOWER RESPONSETIMEOFCHILDREN AGEDORDISABLEDPERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDRENTOUSEAHOTWATERTAP...

Page 21: ...essure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure gauge and replace...

Page 22: ...when removed New pipe collars will insure that the seal is such as to prevent leakage of flue products when properly installed NOTE Anode rod inspection may need to be made more frequently in areas s...

Page 23: ...calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing Check that main manual gas shutoff valve is fully open...

Page 24: ...e complete model and serial number as it appears on the product Refer to the part s list for more information SERVICE The installer may be able to observe and correct certain problems which may arise...

Page 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Page 26: ...n Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dr...

Page 27: ...so installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited...

Page 28: ...28 Copyright 2011 Lochinvar LLC All rights reserved 300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com...