background image

Revision Notes:  Revision A (ECO C03746) initial release.  

Revision B (ECO C12077) reflects the update of ignition timing 
information on page 9.

SBR-USER Rev B

01/13

Summary of Contents for 000 BTU/HR

Page 1: ...or flammable vapors are likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a near by phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified instal...

Page 2: ...ndicates a potentially hazardous situation which if not avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents HAZARD DEFINITIONS 2 PLEASE READ BEFORE PROCEEDING 3 4 1 MAINTENANCE SCHEDULE 5 Maintenance Procedures 6 Appliance Must Be Serviced and Maintaine...

Page 3: ...ed by too much water velocity through the tubes and is not covered by the manufacturer s warranty see Boiler Flow Rates and Temperature Rise for flow requirements Checking equipment Upon receiving equipment check for signs of shipping damage Pay particular attention to parts accompanying the appliances which may show signs of being hit or otherwise being mishandled Verify total number of pieces sh...

Page 4: ...ll be installed in accordance with those installation regulations in force in the local area where the installation is to be made These regulations shall be carefully followed in all cases Authorities having jurisdiction shall be consulted before installations are made In the absence of such requirements the installation shall conform to the latest edition of the National Fuel Gas Code ANSI Z223 1...

Page 5: ... tank Check control settings Check wiring and connections Flame inspection stable uniform Check flue gas passageways Inspect and clean the burners Perform start up check out and performance verification per Section 6 Startup of the Solution Installation and Service manual If combustion or performance indicate need Clean heat exchanger Remove and wash burners ANNUAL START UP Owner maintenance see p...

Page 6: ...ontaining chlorine or fluorine if allowed to contaminate the appliance intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to continue WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified service technician can result in vent system failure causing severe personal injury or death Check vent pipin...

Page 7: ...Solution Installation and Service Manual The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge 2 Read the boiler pressure temperature gauge to make sure the system is pressurized Lift the relief valve top lever slightly allowing water to relieve through the valve and discharge piping 3 If water flows freely release the le...

Page 8: ...t has been under water must be replaced Operating Instructions 1 STOP Read the safety information first 2 Remove the control panel door 3 Set the thermostat to the lowest setting OFF 4 Turn off all electrical power to the appliance 5 This appliance is equipped with an ignition device which automatically lights the pilot DO NOT try to light the pilot by hand 6a 45 000 135 000 Btu hr models rotate t...

Page 9: ...hermostat to highest setting 3 Turn electric power ON 4 Pump relay pulls in to start pump 5 The ignition will begin sparking at the pilot 6 The ignition module will lock out after the trial for ignition period 7 Immediately call a qualified serviceman or installer to repair an ignition system that fails to lock out and properly shut down burner operation 8 After successful completion of the test r...

Page 10: ...10 NOTES ...

Page 11: ...NOTES 11 ...

Page 12: ...Revision Notes Revision A ECO C03746 initial release Revision B ECO C12077 reflects the update of ignition timing information on page 9 SBR USER Rev B 01 13 ...

Reviews: