Assembly instructions | LK Wired Room Control NC

LK Room Thermostat NC, 24 V AC

The LK Room Thermostat NC should be installed 
indoors 1.5 m above fl oor level. Avoid installation 
where its function might be affected (e.g. direct 
sunlight, vents etc.). Lit LED indicates that the 
room thermostat is requesting heat. Wiring bet-
ween the LK Room Thermostat NC and the LK 
Connection Box NC should be carried out using a 
cable such as a signal cable EKKX 4 x 0.5 mm² in 
which case one wire remains unused. The signal 
cable is connected to terminals 1, 2 and 4 on the 
room thermostat and to terminals 1, 2 and 4 in the 
connection box.

LK Room Thermostat NC white and LK Room Thermostat 
NC Dti silver grey.

When installing in a public area, a room thermo-
stat with a concealed temperature dial may be 
used namely the LK Room Thermostat Dti. The 
temperature dial is then placed inside the ther-
mostat cover.

Options

An LK Remote Sensor is used when regulating 
the fl oor temperature. The sensor is placed in the 
fl oor (refer to special instructions attached to the 
room thermostat).

An LK Protection cover protects against external 
damage to the LK Room Thermostat NC. The co-
ver is made of transparent Plexiglas.

LK External Temperature Sensor

LK External Sensor i intended for usage with LK 
Room Thermostat NO or LK Room Thermostat 
Dti NO when the fl oor temperature is to be ad-
justed. 

Remote switching

The LK Control is a complete unit for outdoor tem-
perature dependent fl ow temperature control and 
adapted for LK’s shunt programs. If LK Control is 
used then the volt free pump relay of LK Connec-
tion box can be connected to LK Control, connec-
tions M and H1. By connecting LK Connection box 
to the LK Control, gives the function that when all 
actuators on the manifold is closed, LK Control will 
close its Control valve (Shunt valve) and stop the 
pump. LK Control will re open the control valve 
and restarts the pump when one or several actua-
tors on the manifold open. For more information 
see assembly instruction for LK Control. 

LK Actuator NC, 24 V AC

LK Actuator NC closes when power is cut. A “sta-
tus” indicator is located on top of the actuator. 
When the indicator is “up” the valve is open.

To aid assembly to the manifold, the actuators are 
supplied “open”. Once an actuator is powered 
(for a minimum of 6 minutes) an internal pin is 
released and the actuator will now operate.

The actuators are wired to “actuator terminals” 
of the mating control zone in the control box. Ter-
minals are marked with a symbol for actuators.

The LK Connection Box NC is fi tted with two dif-
ferent sized terminals for actuators. The lower 
terminals are marked zone 5-8, these are inten-
ded for zones with one or two (max.) actuators. 
The upper terminals are marked zone 1-4 and 
have larger terminals to take up to four actuators 
per terminal. A total of fi ve LK Actuators NC may 
be connected to each terminal with the aid of ex-
ternal connector.

LK Actuator NC.

Summary of Contents for Wired Room Control NC

Page 1: ...ators are signalled via the connection box Settings requirements All distribution flows must be adjusted according to the installation guide for the unit The heat set tings for the control unit are regulated according to the requirements of the heat system and the cli mate zone A control zone consists of 1 LK Room Thermostat NC that can control one or more un der floor heating areas each equipped ...

Page 2: ...ure is to be ad justed Remote switching The LK Control is a complete unit for outdoor tem perature dependent flow temperature control and adapted for LK s shunt programs If LK Control is used then the volt free pump relay of LK Connec tion box can be connected to LK Control connec tions M and H1 By connecting LK Connection box to the LK Control gives the function that when all actuators on the man...

Page 3: ...d is connected to the room thermostat as instructed above Floor heating in secondary spaced boarding Place a conduit right between two heat distribu tion plates attach the conduit on the edge of the secondary spaced boarding using a clip for con duits Take into consideration that the placement is at a representative point for the area that is going to be adjusted The external sensor is slip ped in...

Page 4: ...ong sides of the floor heating installation facing the nearest short end Place the conduit at the short end between two heating pipes and end it approx 2 meters in Seal the end of the conduit with tape or similar to pre vent concrete from getting into the conduit The external sensor is slipped into the conduit before pouring the concrete and is connected to the room thermostat as instructed above ...

Page 5: ...ectric connections LK Connection Box NC L N zone 2 zone 5 1 4 zone 4 2 1 1 4 zone 1 6 2 4 2 1 7 4 1 zone 2 2 4 zone 1 2 3 zone 2 1 8 4 1 zone 4 4 2 200 mAT 4 A pot free 200 mAt 4 A pot free N L N L zone1 2 4 1 230 V 24 V 40 VA Transformer 98927 2 1 4 ZONE 1 ZONE 2 ZONE 2 ZONE 1 2 1 98927 2 1 4 1 2 1 7 2 3 4 5 6 7 9 11 10 8 Sample connections for a zone Terminal 1 9 on the room thermostat is connec...

Page 6: ...6 English Wiring with LK Shunt LK Zone Valve and Time Switch if req d LK Connection Box with LK Shunt and LK 2 port Zone Valve 10 Mar 06 EN 33 C 28 0904 Assembly instructions LK Wired Room Control NC ...

Reviews: