8 (10)

EN.31.C.5.1907

Assembly instructions | LK Control Unit ETO2

Settings

Settings are made under the heading

 Setup

. The menu becomes accessible by pressing the MF button once, 

when the unit's display is in normal view. Thereafter, select 

SETUP

 and confirm with the MF button. 

Below is a list of the different menus available under 

SETUP

 

and the options available under the menus.

Function

Description

Selectable value

FORCE HEAT

Used to force the snow melting to start. Snow melting is 

activated for the time given under the heading 

Afterrun

.

Select ON or OFF.

SELECT SCALE

Indicates the temperature scale to be used

Select C or F.

SET TEMP 1

For the unit to start, the temperature must be below the 

given value. (The value refers to ground sensor 1.) 

Select between -20 - + 50 ºC. 

D 3 ºC 

SET TEMP 2

For the unit to start, the temperature must be below the 

given value. (The value refers to ground sensor 2.)

Select between -20 - + 50 ºC. 

AFTERRUN 1

Indicates how long the unit continues to operate after ground 

sensor 1 perceives the ground surface as dry.

Select from 0 minutes to 18 hours.

AFTERRUN 2

Indicates how long the unit continues to operate after ground 

sensor 2 perceives the ground surface as dry.

Select from 0 minutes to 18 hours.

SET TEMP 1

Lowest start temperature for ground sensor 1.

Select between -20 up to the adjusted 

SET TEMP 1 or OFF (OFF = no limit.)

SET TEMP 2

Lowest start temperature for ground sensor 2.

Select between -20 up to the adjusted 

SET TEMP 2 or OFF (OFF = no limit.)

OFFSET T1

Used to calibrate ground sensor 1, see 

Calibration

 heading. Select between -5 to + 5 ºC

OFFSET T2

Used to calibrate ground sensor 2, see

 Calibration 

heading. Select between -5 to + 5 ºC

OFFSET OUT

The function is not used for snow melting.

-

MIN WATER

Indicates the lowest return temperature for the system. On 

delivery, the unit is provided with a resistor instead of a re-

turn temperature sensor. The resistor corresponds to a fixed 

return temperature of 30 ºC. 

Select between 0 and 40 ºC.  

D 3 ºC

MAX WATER

States the highest supply temperature for the system.

NOTE!

 MAX VALUE is 50 ºC for LK Snow melting.

Select between 0 and 60 ºC. 

FACTORY RESET Reset the unit to factory setting.

Select EXIT or RESET

Sensor Heat Auto

When snow melting is activated, the heat-supply to the 

sensor is switched off. In case of extreme circumstances, 

heating of the sensor may occur continuously.

Select Auto or ON

MOIST CTRL

The ground sensor's moisture sensor can be switched off. 

Then the power on/off of the snow melting is controlled only 

on the basis of the set temperature. 

NOTE!

 When OFF is selected, the energy consumption 

increases significantly. 

Select ON or OFF

SENSITIVITY

The sensor's moisture sensitivity has five settings.

MN, LOW, NORM, HIGH and MAX

REINSTALL

Facilitates re-installation of the unit. CODE is 1202. 

-

EXIT

Exit menu setup.

-

Summary of Contents for ETO2

Page 1: ...ly as LK Snow melting must be controlled in termittently The equipment consists of LK Con trol Unit ETO2 LK Ground sensor ETOG and LK Pipe sensor ETF LK Control Unit ETO2 offers the following Energy efficient control of the snow melting system Simple menu navigation Clear background lit display Alarm relay Note The control unit can depending on how it is set either maintain regulate the flow tempe...

Page 2: ...nfirm by pressing the MF button 4 Set Outdoor sensor to OFF confirm by pressing the MF button 5 Set Application to Water based confirm by pressing the MF button 6 The unit changes to normal view and the Adjustment to start stop of external control equipment First time the control unit is charged it must be adjusted to the snow melting system The adjust ment is done with the unit s multifunction bu...

Page 3: ...peration 7 Check that MY Water is set to 5 degrees see the heading Settings 8 Before the system is started the maximum temperature value must be controlled see the heading Settings MAX WATER Read more about sensor 2 under the heading Ground sensor Principle drawing control via 3 way valve ...

Page 4: ... Ground sensor ETOG to the control unit but in some cases two ground sensors may be required to achieve a satisfactory function for example a ground area that stretches around the building and thereby extends to both North and South locations Placement in the ground 1 LK Ground sensor ETOG must be placed in the ground within the heated area where snow ice is suspected to remain for the longest dur...

Page 5: ... this Terminal number LK Pipe sensor return 29 Electrical conductor any color 30 Electrical conductor any color The sensor has no polarity Calibration of the ground sensor If necessary the temperature value for the ground sensor can be calibrated according to the instruc tions below 1 Disconnect the sensor cables that are con nected to terminals 11 and 12 Feed to heat element 2 Wait for a few hour...

Page 6: ...mote control of forced start is connected between terminals 35 and 36 FORCED CONTROL HEAT ETO2 Remote control forced standby Forced Standby is used when you don t want the unit to start even if there is a need On activated input closed contact a forced standby is activat ed The function is connected between terminals 33 and 34 Actuator LK Control unit ETO2 sends control signals to impact the 0 10 ...

Page 7: ...ated for zone 1 OFF Heating deactivated for zone 1 ZONE 2 ON Heating activated for zone 2 OFF Heating deactivated for zone 2 SENSOR 1 Shows the ground temperature for ground sensor 1 Note Does not show the air temperature SENSOR 2 Shows the ground temperature for ground sensor 1 Note Does not show the air temperature MOIST 1 Moisture status for sensor 1 YES NO or blank value Blank value is display...

Page 8: ... up to the adjusted SET TEMP 1 or OFF OFF no limit SET TEMP 2 Lowest start temperature for ground sensor 2 Select between 20 up to the adjusted SET TEMP 2 or OFF OFF no limit OFFSET T1 Used to calibrate ground sensor 1 see Calibration heading Select between 5 to 5 ºC OFFSET T2 Used to calibrate ground sensor 2 see Calibration heading Select between 5 to 5 ºC OFFSET OUT The function is not used for...

Page 9: ...tion RETURN TEMP LOW Too low return temperature SUPPLY TEMP HIGH Too high flow temperature RETURN SENSOR Defect return sensor SUPPLY SENSOR Defect supply sensor TEMP SENSOR 1 Defect ground sensor 1 TEMP SENSOR 2 Defect ground sensor 2 OUTDOOR SENSOR Defect outdoor sensor SENSOR HEATER Short circuiting of the heating element in the ground sensor FROST PROTECT Frost protection activated due to retur...

Page 10: ...LK Pipe sensor supply Brown cable 29 LK Pipe sensor return Blue cable NOTE LK Pipe sensor 2 is connected only if needed see the head ing LK Pipe sensor ETF 30 LK Pipe sensor return Brown cable NOTE LK Pipe sensor 2 is connected only if needed see the head ing LK Pipe sensor ETF 31 32 Not used 33 34 GSM switch or other remote control Remote standby closed contact switches of snow melting in ad vanc...