Living Flame Thermoflow Fireplace Installation Instructions Page 38
Living Flame 2012
Gasfitter
Gas Connection
A gas certificate must be given for the installation, connection and the
associated flue vent system.
All installation work should be carried out by a suitably trained and qualified
person to comply with installation code ASNZS5601 and then certified by a
Craftsman Gasfitter.
Before installation commences, check the data plate on the fire to verify that
the fire is set up to suit your type of gas supply. Field conversion to suit a
different gas is not always practical.
This fireplace is supplied with a 10mm soft copper connection mounted at the
bottom right hand side of the fireplace (as seen from the front).
A gas line capable of supplying a minimum of 50MJ/h should be brought to the
fireplace with a 10mm soft copper tail. This is to be connected to the 10mm
soft copper pipe.
Other systems of connection may be used in accordance with ASNZS5601.
Gas Supply
Inlet Standing Pressure
Set Up Pressure
Natural Gas
2.0 kPa
HIGH 1.0 kPa
LOW
0.5 kPa
LPG Propane
2.75 kPa
HIGH 2.5kPa
LOW
1.5kPa
Maximum Inlet Pressure
4.0 kPa
If inlet pressure exceeds 4.0 kPa, then damage will occur and may result in a
hazardous condition.
Test Pressures
-
Test nipple is located on the injection elbow before the main burner and
on the control
valve for LPG.
-
When electronic controls are fitted, test nipples will be located on the
gas control valve, on both the gas inlet and the gas outlet.
Summary of Contents for Thermoflow
Page 2: ...Living Flame Thermoflow Fireplace Installation Instructions Page 2 Living Flame 2012...
Page 18: ...Living Flame Thermoflow Fireplace Installation Instructions Page 18 Living Flame 2012 Notes...
Page 42: ...Living Flame Thermoflow Fireplace Installation Instructions Page 42 Living Flame 2012 Notes...
Page 49: ...Living Flame Thermoflow Fireplace Installation Instructions Page 49 Living Flame 2012 Notes...