Living Flame Thermoflow Fireplace Installation Instructions Page 26
Living Flame 2012
Owner / Gasfitter / Architect / Builder
Clearance for Combustible Mantel
15
450mm Vertical Clearance
Top of Fire
Underside of Mantel
Selected Combustible Mantel
outside 15° line from the top of
the fire box
Otherwise
non
combustible
mantel may be located lower
Trim