2.3 Duct Circuit
2.3.1 VAV Series Duct Layout Requirements
• Duct pressure operating range of the VAV series indoor units is 60 Pa ~ 200 Pa.
• Care should be taken to minimise changes in speed or direction.
• Care should be taken to keep the velocity within supply ducts below 6 m/s.
• Fan and coil can be split to meet structural challenges.