Status
LED 1 (Input) Green Color
LED 2 (Output) Bicolor
AC_LOSS
Off
Off
Vin_OV_Fault
Off
Off
Vin_UV_Fault
Off
Off
AC_Normal
Solid Green
Solid Green
ALL_Normal
Solid Green
Solid Green
Vout_OV_Warning
Solid Green
Blink Green
Vout_UV_Warning
Solid Green
Blink Green
Iout_OC_Warning
Solid Green
Blink Green
OT1_Warning
Solid Green
Blink Green
OT2_Warning
Solid Green
Blink Green
OT3_Warning
Solid Green
Blink Green
PSON
Solid Green
Blink Yellow
FAN_LOCK
Solid Green
Solid Yellow
Vout_OV_Fault
Solid Green
Solid Yellow
Iout_OC_Fault
Solid Green
Solid Yellow
OTP_Fault
Solid Green
Solid Yellow
Vout_UV_Fault
Solid Green
Solid Yellow
LATCH_SD
Solid Green
Solid Yellow
SCP_Fault
Solid Green
Solid Yellow
STB_UV_Fault
Solid Green
Solid Yellow
STB_OV_Fault
Solid Green
Solid Yellow
STB_OCP_Fault
Solid Green
Solid Yellow
STB_OTP_Fault
Solid Green
Solid Yellow
Shelf Controller Installation (Optional)
While optional, the shelf controller is necessary for system communication to the power system created by
the power shelf along with a battery shelf. The shelf controller is an integral part of a complete DC UPS
system with communication capabilities. It provides communication to the Lite-On Site Monitoring
Controller (SMC) or other monitoring software for information and/or event-based responses.
On the front of the power shelf is a slot for the Shelf Controller. As shown below, a Shelf Controller is held
in place with a spring latch.
LED 1 Input Power
LED 2 Output Power