LION CEBR Series Installation Manual Download Page 9

Thermostat Anticipator

The thermostat anticipator setting recommended is 0.2 amps. Failure to correctly adjust this
setting may result in  unsatisfactory comfort conditions,  and could result in  damage to the
thermostat.

This setting may have to be adjusted slightly to ideally match the boiler control system to the
thermostat, as well as overcome the normal inertia of the radiation system. A setting to low
will   be   characterized   by   a   short   cycle,   which   does   not   allow   the   room   temperature   to   be
satisfied before the boiler shuts down. A setting too high will be characterized by a long cycle,
which allows the room temperature to rise too high before the boiler shuts down. Adjustments
should be made to the setting, if required, but should not exceed 0.1 amps per adjustment.

Newer   electronic   thermostats   typically   have   provisions   for   the   cycle   length,   and   type   of
heating system. The instructions for the thermostat should be followed.

In zoned systems where the thermostat is controlling a zone valve, or circulation pump and not
the boiler, the anticipator should be set to match the current draw of the zone valve being used.

Temperature Control Setting

The boiler has a temperature control knob know as an aquastat on the left hand side. This sets
the maximum temperature that the boiler will operate at. The internal control system monitors
the water temperature in the tank and modulates the heating elements to maintain the water
temperature.   Note   that   the   setting   on   the   knob   only   sets   the   maximum   temperature,   it   is
normal   for   the   boiler   to   operate   at   lower   temperatures   than   this   setting   at   times,   this   is
especially true in the spring and fall when it is not so cold outside. The actual temperature
setting will be determined by the type of heating system the boiler is installed in.

Outdoor Temperature Sensor Connection

The outdoor temperature sensor should be mounted in a suitable location outside the building
where it will be exposed to the outside air. Mount the sensor high enough so it will not be
covered by snow or ice, and in a location where it will not be exposed to direct sunlight.

The   outdoor   temperature   sensor   is   connected   to   the   terminals   “OD   STAT”   on   the   control
circuit board (see Fig. 4 and Fig. 5).

9

Summary of Contents for CEBR Series

Page 1: ...an appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEBR Series Boiler Installation Manual CEB...

Page 2: ...2...

Page 3: ...le phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to the L1 L2 a...

Page 4: ...he aquastat By modulating the boilers heat output based on both the indoor and outdoor temperature your CEBR model provides you with the ultimate in indoor comfort The graph below is an example with t...

Page 5: ...8 11 11 25 208 3 31 2 40 32 CEBR 208 15 14 7 208 3 40 8 60 48 CEBR 208 22 22 5 208 3 62 5 100 80 CEBR 208 30 29 4 208 3 81 6 125 100 CEBR 600 9 9 600 3 8 7 15 12 CEBR 600 15 14 7 600 3 14 1 20 16 CEBR...

Page 6: ...g system Pressure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system...

Page 7: ...r the boiler 3 Though the unit is suitable for floor or wall mount only faces indicated as Zero Clearance may be mounted against combustible surfaces 4 Units must be mounted straight as shown in Fig 2...

Page 8: ...block lower right terminal block see Fig 4 and Fig 5 The pump starts when the thermostat terminals on the control board are closed and stops when these terminals are opened If desired the pump may be...

Page 9: ...on pump and not the boiler the anticipator should be set to match the current draw of the zone valve being used Temperature Control Setting The boiler has a temperature control knob know as an aquasta...

Page 10: ...and thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in removing air from the entir...

Page 11: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Page 12: ...that Boiler The obligation of the Manufacturer to repair replace or refund the purchase price exists provided the defective part or complete unit is returned to the Manufacturer ANY AND ALL TRANSPORT...

Page 13: ...ITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY THE MANUFACTURER S LIABILITY ON ANY CLAIM OF ANY KIND INCLUDING NEGLIGENCE WITH RESPECT TO THE GOODS OR SE...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler Check it for continuity Replace with a new fuse of the correct type if necessary b Otherwise replace the exist...

Page 21: ...e sure the boiler and the heating system are completely full of water a Unplug the low water cut off from the control board Temporarily no more than one second place a jumper wire across the two pins...

Reviews: