Page 5 / 12 

3  Technical Data 

 

S01-72/1000 

Input 

Input voltage range 

AC 3 x 340-550V 

Power frequency 

50/60Hz 

Efficiency 

typ. 91,5% 

Input current limitation 

< 35A

peak

 typ. in cold state, < 70A

peak

 in hot state 

Internal fuse 

3 x 6.3AT 

External branch circuit 

16A (IEC), 20A (USA) necessary 

Output 

Preset range Vo 

56 - 80VDC 

factory setting Vo

nom

 ± 0,15/0,2V 

Max. output power 

1000W 

Powerboost > 0.5s - 2s 

boost break necessary, see diagram in chapter 7 

Powerboost < 0.5s 

no boost break necessary, but the boost time in the last 4s may not be 

longer as 2s, otherwise a boost break 1min is necessary (boostbreak 

<25ms will be not recognized) 

Operation indicator 

green LED for Vo, red LED for error 

Ripple 

40mVss typ. 

Noise voltage 

200mVss typ. 

Temperature coefficient 

≤ 0,025% / K 

Switch on / switch off 

No Vo overshoot (soft-start) 

Start-up delay 

250 ms typ. 

Rise time 

20ms typ./155ms typ.bei 50.000 μF Last 

Back feeding voltage 

approx. 100VDC 

Serial connection 

yes, max. 2 identical power supplies 

Parallel connection 

yes, max. 3 identical power supplies 

Regelung 

Line regulation 

< 0.3% for Vo at Ue

min

 - Ue

max

 

Load regulation 

< 0,5% for Vo at Io 0 - 100% single operation 

< 3% for Vo at Io 0 - 100% parallel operation 

Response time 

typ. 1ms at Io 20 - 80% 

Protection and Controlling 

Overvoltage protection (OVP) 

approx. 87V  

automatical repeating 

Current limitation 

see diagramm, output permanent short-circuit proof 

Overtemperature 

Switches off if inside temperature becomes  

to high, reconnection with hysteresis 

Mains buffering 

11 ms typ. in normal operation 

Relay contact 

Relay contact (<80V/0.2A), changing 

at Vo < 37 / 52V from OK to FAIL 

Control signal OFF 

external switch-off with 5 - 63VDC/5mA

min

 

or switch from Vo 

Summary of Contents for S01-72/1000

Page 1: ...NTI AG LinMot Dok Nr 0185 0077 E_2V1_IG_Power_Supplies_S01_72_1000 Installation Guide Power Supply ENG Power range 1000 W Type S01 72 1000 ...

Page 2: ...Liability 3 1 5 Copyright 3 2 Safety instructions 4 3 Technical Data 5 4 Operating data 6 5 Mechanics 6 5 1 Connection 6 5 2 Mounting 7 6 Explanation of symbols 7 7 Notes 8 7 1 Context between powerboost time and minimum break time 8 7 2 Current limiting characteristic 8 8 Dimensions 9 9 International Certificates 9 10 Declaration of Conformity and CE marking 10 11 CB Test Certificate 11 ...

Page 3: ...ages and expenses caused by incorrect use of the products This also applies to false applications which are caused by NTI AG s own data and notes for example in the course of sales support or application activities It is the sole responsibility of the user to check the information and information provided by NTI AG regarding their safety relevant correctness In addition the entire responsibility f...

Page 4: ...liance To ensure safe performance and avoid any possible risk of damage to the assembly itself and or connected equipment provision must be made for adequate heat dispersal Please observe the relevant instructions in this document and the appliance Please take note of the information shown on the connection and pin configurations for this appliance Pay particular attention to the information on th...

Page 5: ...se voltage 200mVss typ Temperature coefficient 0 025 K Switch on switch off No Vo overshoot soft start Start up delay 250 ms typ Rise time 20ms typ 155ms typ bei 50 000 μF Last Back feeding voltage approx 100VDC Serial connection yes max 2 identical power supplies Parallel connection yes max 3 identical power supplies Regelung Line regulation 0 3 for Vo at Uemin Uemax Load regulation 0 5 for Vo at...

Page 6: ...4 3 EN 55022 EN 55011 class B Radiation depends on assembly Weight 2 0 kg 4 Operating data Temperature range 25 C 70 C integral temperature controlled fan air intake bottom up fan swichted on off in two steps dependent on temperature Derating 2 K at 60 C Operation in any assembly position possible The distance between the surrounding components and the air admission and air exit holes should be at...

Page 7: ... any assembly position possible The distance between the surrounding components and the air admission and air exit holes should be at least 50 mm Please ensure that exhaust air is not immediately sucked in again 6 Explanation of symbols PE Protective conductor Do not use supply without PE connection L1 L2 L3 Mains phases Load connection Relay OK FAIL Monitoring connections OFF Control connection ...

Page 8: ... AG LinMot 7 Notes 7 1 Context between powerboost time and minimum break time 7 2 Current limiting characteristic Start up takes place with power boost between 190 and 210 of the nominal current for a period of approx 2s You can use power boost also in running operation ...

Page 9: ...Installation Guide Power Supply ENG NTI AG LinMot Power range 1000 W Page 9 12 8 Dimensions in mm 9 International Certificates ...

Page 10: ... 72V 1000W 3x340 550VAC 0150 1872 konform ist mit den Anforderungen der Richtlinien is conform to the provisions of directives est conformé aux exigences des directives 2014 35 EU LVD 2014 30 EU EMCD gestützt auf die folgenden Normen based on the following standards base aux normes suivants EMCD EN61000 6 2 2005 EN61000 6 3 2007 A1 2011 SAFETY IEC 60950 1 2005 second edition A1 2009 A2 2013 EN 609...

Page 11: ...Installation Guide Power Supply ENG NTI AG LinMot Power range 1000 W Page 11 12 11 CB Test Certificate ...

Page 12: ...kerstrasse 2 CH 8957 Spreitenbach Sales Administration 41 0 56 419 91 91 office linmot com Tech Support 41 0 56 544 71 00 support linmot com Tech Support Skype skype support linmot Fax 41 0 56 419 91 92 Web http www linmot com LinMot USA LinMot USA Inc N1922 State Road 120 Unit 1 Lake Geneva WI 53147 Sales Administration 262 743 2555 E Mail usasales linmot com Web http www linmot usa com ...