![LinMot E1130-DP-HC User Manual Download Page 4](http://html.mh-extra.com/html/linmot/e1130-dp-hc/e1130-dp-hc_user-manual_1925383004.webp)
LinMot
PROFIBUS Interface
1 System overview
The LinMot PROFIBUS drives E1130-DP, E1230-DP and E1430-DP are PROFIBUS-DP
slaves.
Further information on PROFIBUS can be found under:
http://www.profibus.com
Programming examples provided by LinMot are listed under:
http://www.linmot.com/index.php?id=141
All baud rates are supported and automatically detected.
2 Installation on Drive
For installing the PROFIBUS-DP firmware on the drive, start the LinMot-Talk software and
press the install firmware button
. Choose the file “Firmware_Buildxxxxxxxx.sct” and
press “Open“. The wizard will guide you through the installation. When asking for the
application software choose “ProfibusDP”:
Press ok and follow the rest of the wizard.
3 Connecting to the PROFIBUS
Pin Assignment of the DP Connector X9:
The PROFIBUS connector is a standard DSBU 9 female with the following pin assignment:
Pin 1 not connected
Pin 6 VP (+5VDC for bus termination)
Pin 2 not connected
Pin 7 not connected
Pin 3 B
Pin 8 A
Pin 4 CNTR-P
Pin 9 not connected
Pin 5 GND
Page 4/25
User Manual PROFIBUS Interface / 15/05/2012
NTI AG / LinMot