LinMot
PROFIBUS Interface
11.4. Change a Parameter of the Drive with the Parameter Channel
Module
Example task: Change the “Maximal Current” (UPID 13A6h) over Profibus while firmware is
running
Add module Parameter Channel [4 Word DI/DO]
As Command ID use 13h “Write RAM Value of Parameter by UPID”, Command Count 1
The UPID of “Maximal Current” is 13A6h. The internal scaling of the current value is 0.001A:
3A (Scaled) = 3000 (Int) = 0000088Bh (HEX)
Word
Description
Value (Hex)
1.
Parameter Channel Control 1301h
2.
Parameter UPID
13A6h
3.
Parameter Value Low
088Bh
4.
Parameter Value High
0000h
Page 22/25
User Manual PROFIBUS Interface / 15/05/2012