5.4 Wiring

For ease of installation, the SC360 comes with a 

CAN connector pack and has two wiring options. 

There is a wire connector located in the middle, 

back of the unit and another one at the front, 

bottom of the unit.
When installing the SC360 using the wall Sub-

base and back connector, follow the steps 

below.  The instructions in Section 5.5 are 

for the CAN connector pack and use with the 

SC360 bottom connector only.
1.  Adjust the length and position of each wire to 

reach the proper terminal on the connector 

block of the Sub-base. Strip 1/4” of insulation 

from each wire. Do not allow adjacent 

wires to short together when connected. If 

stranded thermostat cable is used, one or 

more strands will have to be cut to allow 

the cable to fit connector. For use with solid 

conductor 18 ga. thermostat wire. 

2.  Match and connect control wires to the 

proper terminals on the connector block.  

 

Refer to the Field Wiring Connection 

Diagrams shown later in this document.

3.  Push excess wire back into the wall and seal 

the hole to prevent air leaks.  

 

NOTE: Air Leaks in the wall behind the 

SC360 can cause improper operation.

4.  Attach the SC360 to the Sub-base.
5.  Turn ON power to the heating and cooling 

equipment.

5.5 Trane & American Standard Link Low Voltage Wire Connectors

Link mode uses simple connectors for low voltage 

connections. These connections are color coded 

which makes the installation easier and quicker.

Wire Colors

R

Red 

DH

White

DL

Green

B

Blue

Do the following to make the connections from the 

actual thermostat wire to the connector.

NOTE: These connectors are necessary at the 

communicating outdoor unit, communicating indoor 

unit, distribution board(s), system controller and 

communicating accessories.
1.  Strip the Red, White, Green and Blue thermostat 

wires back 1/4”.

2.  Insert the wires into the connector in the correctly 

colored locations.

3.

  When you feel it release, allow each wire to 

slide in further.

4.  Pull back on the wires individually and slightly 

and check if the wires are seated properly. If 

each wire does not pull out for all four wires, the 

connection is complete.

5.  Connectors are ONE-TIME-USE ONLY. If the 

thermostat wire gets broken off inside of the 

connector, the connector must be replaced. If a 

wire color gets inserted into the wrong connector 

position, it may be possible to work the wire back 

out of the connector.  

DO NOT REUSE THE CONNECTOR – 

REPLACE IT INSTEAD.

6.  Wire colors are for illustration purposes only. 

If using a different color, ensure it lands at 

the correct terminal throughout all of the 

communicating control wiring.

Connect the CAN connector into the male coupling 

on the low voltage harness at the Outdoor unit.
The air handler has two dedicated CAN Connector 

headers on the Air Handler Control (AHC) board. In 

Link communicating mode, both of them are in the 

communicating loop. It does not matter which one 

goes to the thermostat, System Controller, distribution 

board, outdoor unit or any other Link accessory.

NOTE: For use with 18 ga. solid core thermostat wire.

RD

HD

LB

CAN Connector

Strip the control

wire back- 1/4”

Summary of Contents for SC360

Page 1: ...instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular p...

Page 2: ...conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the interpretation of this information nor can it assume any liability in...

Page 3: ...ange Ambient Temperature 40 F to 141 F including dead band 38 F to 132 F excluding dead band External Ambient Temperature up to 136 F Indoor Humidity Display Range 0 to 100 1 resolution Minimum Cycle...

Page 4: ...he SC360 including pushing additional features out to the installed communicating equipment No dealer visit or SD cards are required Technical Advantages Self configuring system on startup Automated v...

Page 5: ...t always install the UX360 diagonally above the SC360 If top left and top right sides are not possible then install the SC360 to the right or left side of the UX360 Keep these 2 devices as far apart a...

Page 6: ...es entertainment centers or shelving units Install the SC360 further than two inches away from any pipes duct work or other metal obstructions Install the SC360 in an area with minimized metal obstruc...

Page 7: ...r Wire Colors R Red DH White DL Green B Blue Do the following to make the connections from the actual thermostat wire to the connector NOTE These connectors are necessary at the communicating outdoor...

Page 8: ...ARD 4x or 8x SC360 R DH DL B R DH DL B R DH DL B COMMUNICATING INDOOR UNIT COMMUNICATING OUTDOOR UNIT R DH DL B RED WHITE GREEN BLUE WIRE COLORS R DH DL B R DH DL B R DH DL B R DH DL B R DH DL B R DH...

Page 9: ...DL will vary depending on bus traffic Resistance Between DH and DL1 Appropriate range can vary depending on the communicating equipment installed on the system Expected Measurement 60 10 ohms can be e...

Page 10: ...P Mode Fast Flashing SoftAP mode enabled Medium Flashing 10 Seconds then OFF SoftAP connection succeeded On Solid 10 seconds then OFF Error Power Up Sequence When the SC360 is connected to the Sub bas...

Page 11: ...n provide a WiFi hotspot to which the Diagnostics Mobile App can connect The app connects to the hotspot the system update is transferred to the controller and the controller can begin updating all th...

Page 12: ...ontroller for at least 6 seconds Step 6 At this point switch to your mobile device s WiFi settings Step 7 Connect to hotspot name hvac_XXXXXX the X s here refers to the last 6 characters of the MAC ID...

Page 13: ...1C EN 13 Step 10 Push update to system and wait for verification that the download was successful Once complete the technician s job is done NOTE This system update will take several hours to complete...

Page 14: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Page 15: ...SC360 System Controller 18 HD95D1 1C EN 15...

Page 16: ...w trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to...

Reviews: