background image

 

SC360 System Controller

18-HD95D1-1C-EN 5

5.1 Location In Controlled Space

 

The SC360 is not required to be installed in 
a controlled space. However, if the SC360 
is located in a controlled space, install it in a 
centrally located climate controlled living space 
with good air circulation and follow the guidelines 
below.
•  In order for the SC360 to be assigned as an 

indoor temperature and humidity sensor, it 
must be installed in a controlled space. 
 
NOTE: See the UX360 Installer Guide for 
details on how to configure the SC360 for a 
controlled space and assign it as an indoor 
temperature and humidity sensor.

•  The SC360 

MUST

 be at least 3 feet apart 

from any other electronic device such as a TV 
or speaker. 

•  If the SC360 is not within the controlled space 

you MUST assign an indoor temperature 
sensor that is installed in a controlled space. 
See the UX360 Installer Guide for details.

•  If the UX360 and the SC360 must be in close 

proximity (closer than 3 feet), always install the 
UX360 diagonally above the SC360. If top left 
and top right sides are not possible, then install 
the SC360 to the right or left side of the UX360.

•  Keep these 2 devices as far apart as possible. 

Never install them on top of each other.

•  The SC360 should be at least 3 feet away 

from a corner where 2 walls meet. Corners 
have poor circulation. 

•  The SC360 should not be directly exposed to 

air currents from supply air or ceiling fans. 

•  Avoid exposing the SC360 to any radiant heat 

source such as sun light or fireplaces.

 5.  Placement & Installation

Incorrect
Placement

3 Feet Min.

UX360

SC360

Preferred placement

(diagonally and above, in

same controlled space)

Acceptable placement

when space is limited

(SC360 to right or left, in

same controlled space)

Unacceptable placement

when space is limited

(Never install above/below,

same controlled space)

3 Feet Min.

3 Feet Min.

3 Feet Min.

3 Feet Min.

Incorrect
Placement

Problematic Air Patterns

Onboard

Thermistor

5 FEET

Optimum
Zone

2 FEET

Correct
Placement

Locate the control in an 

area with minimal air flow 

patterns thereby avoiding 

interuption of natural heat 

dissipation

Figure 1.  Placement of SC360

Summary of Contents for SC360

Page 1: ...instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular p...

Page 2: ...conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the interpretation of this information nor can it assume any liability in...

Page 3: ...ange Ambient Temperature 40 F to 141 F including dead band 38 F to 132 F excluding dead band External Ambient Temperature up to 136 F Indoor Humidity Display Range 0 to 100 1 resolution Minimum Cycle...

Page 4: ...he SC360 including pushing additional features out to the installed communicating equipment No dealer visit or SD cards are required Technical Advantages Self configuring system on startup Automated v...

Page 5: ...t always install the UX360 diagonally above the SC360 If top left and top right sides are not possible then install the SC360 to the right or left side of the UX360 Keep these 2 devices as far apart a...

Page 6: ...es entertainment centers or shelving units Install the SC360 further than two inches away from any pipes duct work or other metal obstructions Install the SC360 in an area with minimized metal obstruc...

Page 7: ...r Wire Colors R Red DH White DL Green B Blue Do the following to make the connections from the actual thermostat wire to the connector NOTE These connectors are necessary at the communicating outdoor...

Page 8: ...ARD 4x or 8x SC360 R DH DL B R DH DL B R DH DL B COMMUNICATING INDOOR UNIT COMMUNICATING OUTDOOR UNIT R DH DL B RED WHITE GREEN BLUE WIRE COLORS R DH DL B R DH DL B R DH DL B R DH DL B R DH DL B R DH...

Page 9: ...DL will vary depending on bus traffic Resistance Between DH and DL1 Appropriate range can vary depending on the communicating equipment installed on the system Expected Measurement 60 10 ohms can be e...

Page 10: ...P Mode Fast Flashing SoftAP mode enabled Medium Flashing 10 Seconds then OFF SoftAP connection succeeded On Solid 10 seconds then OFF Error Power Up Sequence When the SC360 is connected to the Sub bas...

Page 11: ...n provide a WiFi hotspot to which the Diagnostics Mobile App can connect The app connects to the hotspot the system update is transferred to the controller and the controller can begin updating all th...

Page 12: ...ontroller for at least 6 seconds Step 6 At this point switch to your mobile device s WiFi settings Step 7 Connect to hotspot name hvac_XXXXXX the X s here refers to the last 6 characters of the MAC ID...

Page 13: ...1C EN 13 Step 10 Push update to system and wait for verification that the download was successful Once complete the technician s job is done NOTE This system update will take several hours to complete...

Page 14: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Page 15: ...SC360 System Controller 18 HD95D1 1C EN 15...

Page 16: ...w trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to...

Reviews: