EI 60 S Installation remote from the vertical rigid wall hole Ø+30
1. Ventilation duct in one piece
2. M8 threaded rod and suspension rings
3. Fire damper
4. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
sealing
5. Self-drilling screw Ø 4,2 X 13 mm x4
6. Rock wool 35 kg/m³, or mortar or plaster putty
7. Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent: see
Installation remote from the rigid wall
8. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
refractory ring
9. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) to cover the sealing
D Hole size: see table above
a 1000mm MAX, n° of threaded rods depending on the length of the duct
(use 1 threaded bar for a≤1000 mm)
EI 60 S Installation remote from the vertical rigid wall hole Ø+10
1. Ventilation duct in one piece
2. M8 threaded rod and suspension rings
3. Fire damper
4. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
construction support
5. Self-drilling screw Ø 4,2 X 13 mm x4
6. Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent: see
Installation remote from the rigid wall
7. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
refractory ring
D Hole size: see table above
a 1000mm MAX, n° of threaded rods depending on the length of the duct
(use 1 threaded bar for a≤1000 mm)
rev 20-12