12
/14
Installation remote from the vertical light wall (plasterboard)
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances .
Before and after installation please perform a functional test. Refer to
section Mechanism type for further information .
Wall opening
A opening must be provided in the wall as indicated in the table and
in the drawing
Damper positioning
Connect fire damper to the galvanized steel duct as indicated in the
drawing.
Install the damper with the mechanism facing away from the wall as
indicated in the drawing.
The fire damper has to be fixed and suspended from the ceiling as
indicated in the drawing.
For distance between fire damper and wall less than or equal to 1m,
only one support is enough as indicated in the drawing.
The support at 20 mm from the fire damper is always mandatory.
Close the blade before installing the fire damper.
Filling
Fill the space between the wall and the damper as indicated in the
table and in the drawing.
Sealing with concrete is not allowed.
Cover the duct over its entire length and fire damper as indicated in
the drawing wrapping it with insulation rock wool Pro Wired Mat 80
AL 1 Paroc with density of 80 kg/m³ and thickness 70 mm or equi-
valent.
A metallic mesh is installed around the rock wool. The junctions
between the insulation and the damper are made by an acrylic fire
stopping sealant (es. Soudal Firecryl or equivalent with resistance
and reaction to fire equal or higher), as indicated in the drawing.
Fire resistance classification
“D” hole size
[mm]
Wall minimum thickness “S”
[mm]
Sealing
EI 60 S Installation remote from the vertical light wall
Wall resistance class EI 60
EI 60 S
(300 Pa)
From Ø + 30 to Ø + 55
95
Rock wool 35 kg/m³ or
mortar or plaster putty and
fire stopping sealant (e.g.
Soudal Firecryl or equivalent
with resistance and reaction
to fire equal or higher)
EI 60 S Installation remote from the vertical light wall
Wall resistance class EI 60
EI 60 S
(300 Pa)
Ø + 10
95
Fire stopping sealant
(reference Soudal Firecryl or
equivalent with resistance
and reaction to fire equal
or higher)
EI 60 S Installation remote from the vertical light wall hole Ø+30
1. Timber studs 45 x 45 mm or metal frame
2. Rock wool density 35 kg/m³ (optional)
3. Plasterboard thickness 12,5 mm type A (EN 520) or higher
4. Ventilation duct in one piece
5. M8 threaded rod and suspension rings
6. Fire damper
7. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
sealing
8. Self-drilling screw Ø 4,2 X 13 mm x4
9. Rock wool 35 kg/m³, or mortar or plaster putty
10. Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent: see
Installation remote from vertical light wall (plasterboard)
11. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) to cover the insulation
12. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
refractory ring
D Hole size: see table above
a 1000mm MAX, n° of threaded rods depending on the length of the duct
(use 1 threaded bar for a≤1000 mm)
rev 20-12
12