EI 60 S Installation remote from the vertical light wall hole Ø+10
1. Timber studs 45 x 45 mm or metal frame
2. Rock wool density 35 kg/m³ (optional)
3. Plasterboard thickness 12,5 mm type A (EN 520) or higher
4. Ventilation duct in one piece
5. M8 threaded rod and suspension rings
6. Fire damper
7. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
construction support
8. Self-drilling screw Ø 4,2 X 13 mm x4
9. Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent: see
Installation remote from vertical light wall (plasterboard)
10. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between insulation and
refractory ring
D Hole size: see table above
a 1000mm MAX, n° of threaded rods depending on the length of the duct
(use 1 threaded bar for a≤1000 mm)