background image

5

/15

 

†

Manual with magnet

1.  Manual opening lever

2.  Manual closing button

3.  Lever position when the blade is open

4.  Lever position when the blade is closed

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct exceeds 

70°C (or 95°C for the fire damper with 95°C thermal fuse).

It is possible to close the damper by pressing the indicated button.

It is possible to remotely close the fire damper.

The manual command mechanism with magnet is equipped with 

an electromagnet which, in case power is interrupted (interuption 

magnet version) or when power is supplied (input magnet version), 

comands the closing of the damper.

Blade opening mode

The damper must be opened when the ventilation system if 

switched off.

In case of closed damper by pressing the closing button or remotely 

by electromagnet, it is possible to manually open the fire damper 

blade by rotating the lever antyclockwise.

In case of closed damper as a result of the action of the thermosen-

sitive element, it is possible to manually reopen the damper by rotat-

ing the lever counterclockwise once the element has been replaced.

Position indication microswitches

It is advisable to install the fire damper with position microswitches 

(S2 optional) which signal the position of the blade (open or closed). 

Refer to the section Electrical connections  for more details.

Closing by remote control

With power supply input or interruption magnet.

Temperature calibration of thermosensitive element for auto-

matic damper closing

70 °C±7 °C (Standard)

95 °C±9 °C (On request).

 

†

Belimo motorized version

1.  Manual closing switch

2.  Manual opening lever

3.  Position indicator

4.  Blade locking lever

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct or in 

the room exceeds 72°C (or 95°C for the 95°C version).

To close the damper when the motor is connected, press the switch 

on the temperature sensor or cut off the power supply.

Blade opening mode

The damper must be opened when the ventilation system if 

switched off.

To open the damper with the electric motor driven actuator, provide 

power supply to the motor. Refer to the section Electrical connec-

tions  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate clockwise to the 90° indicator. To hold the damper in open 

position operate on the lever indicated in figure.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade's position (open or closed). Refer to the section Elec-

trical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

 

†

Siemens motorized version

1.  Manual closing switch

2.  Manual opening lever

3.  Screwdriver

4.  Position indicator

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct or in 

the room exceeds 72°C (or 95°C for the 95°C version).

To close the damper when the motor is connected, press the switch 

on the temperature sensor or cut off the power supply.

Blade opening mode

The damper must be opened when the ventilation system if 

switched off.

To open the damper with the electric motor driven actuator, provide 

power supply to the motor. Refer to the section Electrical connec-

tions  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate counterclockwise to the 90 °C indicator. To hold the damp-

er in open position, rotate the screw anticlockwise as shown in the 

picture.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade's position (open or closed). Refer to the section Elec-

trical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Summary of Contents for EI 120 S

Page 1: ...l data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WKS25 500 Pa Cert N 1812 CPR 1046 EN 15650 This is a 15 page installation booklet...

Page 2: ...sity 995 kg m Plasterboard sealing ve i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 120 S Installation within vertical light wall gypsu...

Page 3: ...l axis Fixing flaps 1 Bend for walls 100 mm thick or higher 2 Bend for walls 70 mm thick or higher Fire dampers pairing The patented WKS25 rectangular fire dampers can be paired side by side or vertic...

Page 4: ...atically closes the blade when the temperature in the duct exceeds 70 C or 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade ope...

Page 5: ...perature sensor or cut off the power supply Blade opening mode The damper must be opened when the ventilation system if switched off To open the damper with the electric motor driven actuator provide...

Page 6: ...Normally open C Common NF Normally closed Manual with magnet MR MI version the magnet is powered using 24 V DC 48 V DC through S0 25 electric board S0 25 electronic board S2 optional for 24V DC 48V DC...

Page 7: ...4V AC DC WKS25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230V AC WKS25VSS Siemens GRA326 Opening 4 5 W In stand by 3 5 W Microswitches position contacts Manual control version 12VDC 2A 125...

Page 8: ...itioning The fire damper can be installed both with the blade axis positioned vertically or horizontally Positioning brackets before fixing 1 Positioning brackets Installation of flexible connectors i...

Page 9: ...L1 L2 200 50 50 250 50 100 300 50 100 350 50 150 400 50 150 450 50 200 500 50 200 550 50 250 600 100 250 H Nominal height of fire damper L1 End cap length mechanism side L2 End cap length mechanism o...

Page 10: ...l floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor of the same type but with greater thickness a...

Page 11: ...tach to the steel pro file underneath 1 Plasterboard thickness 12 5 mm 2 Rock wool density up to 100 kg m optional 3 Horizontal U shaped profile 4 Vertical C shaped profile 5 Self drilling screw 3 5 X...

Page 12: ...located on the fire damper casing See section Fixing flaps for further details Position the damper in the opening so that the side of the closing mechanism extends from the wall by 185 mm Be careful n...

Page 13: ...r both in relation to air flow and the side with the higher probability of exposure to fire as indicated in standard EN1366 2 paragraph 6 2 Filling It is not necessary to insert any material but simpl...

Page 14: ...5 mm 2 Self drilling screw 3 5 X 45 mm EI 120 S Installation within vertical light wall gypsum blocks wall The WKS25 fire dampers classified EI 120 S within vertical light walls built with gypsum bloc...

Page 15: ...al wall Installation within vertical light wall Shaft wall WKS25 fire dampers are tested and approved in Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall m...

Reviews:

Related manuals for EI 120 S