2
/15
OVER VIEW
Fire resistance classification according to EN 13501-3-2009
EI 120 S
(500 Pa)
EI 90 S
(500 Pa)
EI 60 S
(500 Pa)
EI 30 S
(500 Pa)
Rigid w
all
EI 120 S Installation within vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Plasterboard and rock wool 100 kg/m³ sealing
ve (i
↔
o)
D
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
Fle
xible w
all
EI 120 S Installation within vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard sealing
ve (i
↔
o)
D
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
EI 90 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plasterboard sealing
ve (i
↔
o)
D
-
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
EI 120 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plasterboard sealing
ve (i
↔
o)
D
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B x H
min 100 x 200
max 800 x 600
B X H are fire damper minimum and maximum nominal dimensions (base x height) in mm
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1046 EN 15650
Installations within vertical light wall (Shaft wall)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Fle
xible w
all
EI 90 S Installation within vertical light wall (Shaft wall)
Wall minimum thickness 90 mm
Plasterboard sealing
ve (i
↔
o)
D
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600