background image

LightAlarms

Tel: (888) 552-6467 

Fax: (800) 316-4515

www.lightalarms.com

06/18 750.1783 Rev. G

9/12

LMIU 125/250/400W Mini Inverter

4. LIGHTING LOAD TESTING

The test is fully automatic. To maintain accurate data, these 2 conditions must be met prior to acquiring values from an all-good lighting load:
• The battery has to be at or near full power. The program will delay data capture for a minimum of 48 hours following any
 discharge or reset.
• The charger will also wait to be in hysteresis mode (charger cycling on/off).       

      

5. AUDIBLE ALARM (BUZZER)   

This option can be activated or de-activated in the field. Refer to Figure 4.
To select the audible alarm option:

a.   Remove all power sources to the board (AC and battery).
b. With long-nose pliers, pull on the shunt (little black box) until it is free from the pins.
c. Put the shunt back in place according to the option selection.
d. Reconnect AC power and the battery.    

6. SERVICE ALARM OPTION (INDICATOR)

If installed, insert each wire of the Building Alarm Panel into separate terminals of the terminal 
block marked “SERVICE ALARM”.
Alarm Panel shall provide a 24V signal. The charger board will indicate a fault by closing a 
contact. Polarity is not specified.

7. LIGHTING CONTROL OVERRIDE 

This feature is used with lighting loads equipped with low voltage dimming control. The dimming 
function must be disabled during a power failure in order for the load to provide a 100% level of lighting.
The circuit consists of a single-pole dry-contact relay that is normally closed in stand-by operation. In emergency mode (power failure) the relay 
contacts open and disconnect the dimming signal from the lighting load, allowing the load to operate at 100% light level.

  

INSTALLATION:

1. Locate the Lighting Control signal cable pair.
2. Cut, strip and extend one wire only, of the Lighting Control signal cable.
3.

Connect to the terminal block marked "LIGHTING CONTROL OVERRIDE" as shown in the wiring diagram below.

 

 

8. UNITS WITH NO AUTO-TEST

This equipment is not self-testing in conformance with the Life Safety Code, ANSI/NFPA 101.    

IMPORTANT:

Must install a minimum lamp load equvivalent to 10% of the rated capacity of the unit. 

Example: 12.5W/VA for a 125W inverter unit.

IMPORTANT:

Only one control signal can be handled by one LCO module. Multi control signals require one LCO per control 
signal. Consult customer service if there is more than one Lighting Control signal to be overridden.

Shunt for 
enable / disable
Buzzer

BUZZER 

‘’Active’’

BUZZER

’’Silent’’

Shunt to 
enable / disable
Buzzer

Figure 4

Master

Lighting
Control

Open(cut) one side of the
Light Control

Lighting Control Cable

Wires to be connected into the
“Lighting Control Overeride”
terminal block. 

LCO

Mini Inverter

LCO Contact Specification:
Max. voltage: 60V
Max. current: 250mA

A.C. load output

from the Mini Inverter.

Figure 5

Lighting Fixtures

(Fluorescent or LED) 

used for emergency 

lighting.

i

Summary of Contents for LMIU 125W

Page 1: ...onal Electrical Code and local regulations 12 The LMIU contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Elect...

Page 2: ...TH NORMAL AND EMERGENCY SOURCES BY TURNING OFF THE A C BRANCH CIRCUIT AND BY DISCONNECTING THE BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARA...

Page 3: ...specting the operating voltage All remote circuitry is to be wired in accordance with Article 700 of the National Electric Code Do not exceed the total rating of the Mini Inverter Unit is rated at max...

Page 4: ...e same color in each pole on the terminal block See Figure on side c Leave a minimum of one inch 25mm between the live voltage cabling and the unsheathed low voltage data cabling NOTE NO WIRING IS REQ...

Page 5: ...e of 20 to 30 C 68 to 86 F their life expectancy is 8 to 10 years However as stated above the equipment must be tested for a minimum of 90 minutes once per year When the batteries will no longer opera...

Page 6: ...tched Neutral Ground Line see note 3 see note 3 Wall Switch Normally ON Lighting Load Output Wiring Triac Dimmer Device Fluorescent LED Incandescent FIGURE 2A WIRING DIAGRAM SWITCHED NORMALLY ON LOAD...

Page 7: ...PUT POWER terminals 4 DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD NEUTRAL Un Switched see note 3 Line 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWITCHED NORM...

Page 8: ...switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting...

Page 9: ...isabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergen...

Page 10: ...not commissioned to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF...

Page 11: ...the batteries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED...

Page 12: ...CT CUSTOMER SERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in t...

Reviews: