LMIU 125/250/400W Mini Inverter

  

SYSTEM OPERATION

• The diagnostic/charger is a self-contained, fully automatic microcontroller-based system.
• Once the installation is complete, it is not necessary to have the AC power energized. Only the battery needs to be connected.
   The unit goes directly into lockout mode and waits for AC power to be restored.

1. ALARM SILENCE / MANUAL TEST / SYSTEM INITIALIZATION

• Alarms are silenced by pushing the “TEST” switch less than one half second. Alarm indication can only be silenced after correcting the
  fault or by re-initializing the system.
• Manual forced tests are initiated by pushing and holding the “TEST” switch more than one second. The 1-minute test will start.
• System initialization is done by holding the “TEST” switch for at least 6 seconds.

2. DIAGNOSTIC AND NEXUS

®

 (OPTION)    

I

f the audible alarm has been activated, any fault condition will produce an audible warning that 

consists of an intermittent beep: one second on, one second off. 
Refer to figure 3 for two lists of possible conditions.

a.   BATTERY DISCONNECT / INVERTER FAILURE

 

The status indicator displays a steady red LED if the battery circuit is open or

 shorted, or if there is an Inverter failure.

b. BATTERY FAILURE

The status indicator displays 1 red blink and a pause of 5 seconds if an incorrect battery 
is installed (e.g. 12V battery on a 6V system), or if the battery has failed a timed or forced 
test (reached LVD level before the end of the test).

c. CHARGER MONITORING

The status indicator displays 2 red blinks and a pause of 4 seconds if the charging cur-
rent does not fall within limits corresponding to the charger command state.

d. LIGHTING LOAD CAPTURE SEQUENCE

The capture sequence is initiated only by a reset of the system. This is done by holding the “TEST” switch for at least 6 seconds. The 
reset also initializes the main counter. This renewal takes place to compensate for system variations when the unit ages. Renewal is not 
allowed if there is a lighting load failure alarm. This is not applicable for units with no auto-test option.

e. SERVER FAILURE

The Nexus server (controller or PC) is no longer communicating with the RF unit’s modem. To solve this issue, you need to verify if the 
Nexus server is up and running. If it is up and running, check to see if other surrounding emergency lighting units are not powered. If they 
are powered off, they will prevent the unit in question to communicate with the modem. Otherwise simply reset the modem.

f. BLINK MODE

A “Blink mode” signal was sent from the Nexus server (controller or PC) to the emergency lighting unit. To stop the “Blink mode”, you 
need to access the Nexus server and execute a stop blink mode operation.

g. NOT COMMISSIONED

The unit was not commissioned and therefore not registered in the Nexus server. Once the unit is commissioned, the auto-test will be dis-
abled and the LED will show a steady green for 10 seconds and steady orange for 1 second.

To cancel a fault condition, after applying all corrective actions, simply reset the unit.
*Refer to Nexus

®

 installation addendum for more details.

   

3. AUTOMATIC UNIT TEST (30-DAY TEST)

Every 30 days, while in charging mode, the sequence generator will generate a command to energize the transfer on the emergency 
lighting circuit for a variable test period depending on the yearly sequence.  

• If the battery fails to complete the discharge test, the charger will display a battery failure and the test will abort.
• The 30-day automatic test sequence is reset every time the lighting load is turned on, including the manual test.

FEATURES AND

 

OPTIONS

IMPORTANT:

Reset the system whenever you add or change the lighting load. To reset the system, press the 
test switch for 6 seconds.

US (MIN)

NOTE:
AUTO-TESTING IS NOT PROVIDED IN SOME UNITS.
REFER TO FEATURE 8. 

Monthly test

1

6 month test

30

12 month test

90

Figure 3

i

Summary of Contents for LMIU 125W

Page 1: ...onal Electrical Code and local regulations 12 The LMIU contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Elect...

Page 2: ...TH NORMAL AND EMERGENCY SOURCES BY TURNING OFF THE A C BRANCH CIRCUIT AND BY DISCONNECTING THE BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARA...

Page 3: ...specting the operating voltage All remote circuitry is to be wired in accordance with Article 700 of the National Electric Code Do not exceed the total rating of the Mini Inverter Unit is rated at max...

Page 4: ...e same color in each pole on the terminal block See Figure on side c Leave a minimum of one inch 25mm between the live voltage cabling and the unsheathed low voltage data cabling NOTE NO WIRING IS REQ...

Page 5: ...e of 20 to 30 C 68 to 86 F their life expectancy is 8 to 10 years However as stated above the equipment must be tested for a minimum of 90 minutes once per year When the batteries will no longer opera...

Page 6: ...tched Neutral Ground Line see note 3 see note 3 Wall Switch Normally ON Lighting Load Output Wiring Triac Dimmer Device Fluorescent LED Incandescent FIGURE 2A WIRING DIAGRAM SWITCHED NORMALLY ON LOAD...

Page 7: ...PUT POWER terminals 4 DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD NEUTRAL Un Switched see note 3 Line 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWITCHED NORM...

Page 8: ...switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting...

Page 9: ...isabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergen...

Page 10: ...not commissioned to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF...

Page 11: ...the batteries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED...

Page 12: ...CT CUSTOMER SERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in t...

Reviews: