LMIU 125/250/400W Mini Inverter
NOTE: THE FOLLOWING WIRING DIAGRAMS HAVE BEEN SIMPLIFIED FOR CLARITY.
ACTUAL POSITION OF COMPONENTS WILL VARY
Line 120Vac
Switched or
Neutral
120V
Neutral
Input Wiring
Ground
Notes:
1. Connect fixture supply and unit ground in accordance with
local and national codes.
2. Single voltage wiring only. Either 120V or 277V. Input and
output voltage must be the same.
3.
DO NOT COMBINE THE INPUT POWER NEUTRAL
WITH THE LOAD NEUTRAL.
Neutral
Lighting Load
Primary
Un-Switched
AC Input
Un-Switched
Neutral
Ground
Line
(see note 3)
(see note 3)
Wall Switch
Normally ON
Lighting Load
Output Wiring
Triac Dimmer
Device
Fluorescent, LED,
Incandescent
FIGURE 2A
WIRING DIAGRAM:
SWITCHED
NORMALLY ON LOAD
Line 120Vac
Neutral
120V
Neutral
Ground
Ground
Neutral
Line
Switched Line(Not Used)
Un-Switched Line
Neutral
(see note 3)
(see note 3)
FIGURE 2B
WIRING DIAGRAM:
NORMALLY OFF LOAD
IMPORTANT:
FOR NORMALLY OFF LOADS:
REMOVE THIS JUMPER WIRE.
Lighting Load
Primary
Un-Switched
AC Input
Normally ON
Lighting Load
Fluorescent, LED,
Incandescent
Notes:
1. Connect fixture supply and unit ground in accordance with
local and national codes.
2. Single voltage wiring only. Either 120V or 277V. Input and
output voltage must be the same.
3.
DO NOT COMBINE THE INPUT POWER NEUTRAL
WITH THE LOAD NEUTRAL.
Input Wiring
Output Wiring