Netlink Installation and Operation Manual
18
19
Installation and Operation
2.2.16 Setting up the Parameters for the Email Reports
The Netlink can send email alerts based on selectable conditions . If enabled, when the selected conditions are met, the Netlink will send
an email with an attached report file (in CSV format) . To set up the email alert conditions, click the "Reporting" link in the top menu .
Select the Email Alert Triggers
The "Alert Enable On" block of the Reporting page contains checkboxes for the various conditions that can cause an email alert to
be sent (See Figure 2 .11) .
System Fault
If checked, a System Fault condition on a connected device will generate an email alert .
AC Fault
If checked, an AC fault condition on a connected device will generate an email alert .
Battery Backup Time
If checked, an alert will be generated if the required standby time is not able to be met with the installed battery .
Current Sensor 1
If checked, a current outside the range set for Current Sensor 1 will generate an email alert .
External Temperature
If checked, an external temperature outside of the range set will generate an email alert . (NL4 Only)
Event1
If checked, a valid input on the Event1 Input will generate an email alert .
FAI Active
If checked, an active FAI Input on a connected device will cause an email alert .
Current Sensor 2
If checked, a current outside the range set for Current Sensor 2 will generate an email report . (NL4 Only)
Battery End of Life
If checked, an email alert will be sent when the Battery Runtime of the connected device reaches the "Rated
Battery Life" setting on the Configure page . When a new battery is installed, the "Reset Timer for New Battery
Installation" box on the Programming page should be set to reset the Battery Runtime counter .
Battery Condition
An email alert will be sent when the battery charge is less than 20% (one yellow bar on the "Bat . Condition"
display on the power supply page) .
ADC1 Reading
If checked, a voltage outside the range set for ADC1 will generate an email report .
Service Reminder
An email alert will be sent when the "Next Service Due" date and time on the Configure page are reached .
Device Detect
An email alert will be sent when a device (FPO, M8) is connected or disconnected from the Netlink board . This
will notify the email recipient if the Netlink loses communication with a connected device .
After setting the email alert triggers, click the "Submit" button at the bottom of the "Alert Enable On" section for the settings to take effect .
Select the Occurrences to Report
The "Select Occurrences to Report" block of the Reporting page allows the setting of the number of history events to be included in
the report file attached to the alert email (See Figure 2 .11) . The Netlink records a snapshot of device parameters at the time period
selected on the Configure page . Up to 1000 history events can be recorded . The user can enter between 1 (the latest event only), up
to 1000 (for all events) . After entering the number of history events to email, click the "Submit" button to save this setting .
Select the Devices and Parameters to Report
The bottom section of the Reporting page contains the devices and parameters selection area (See Figure 2 .11) . Any connected
devices will show here, along with a section for the Netlink itself .
The Netlink and each device also have selectable parameters listed below their headings . Checking these parameters will add them
to the report attached to the email alert . These are the same parameters as seen on the Home page .
Available Netlink parameters include: enclosure temperature, external temperature, current sensor readings, the ADC1 reading, and the
Event Status (these may appear as the labels set on the Configure page) .
Available FPO parameters include: Model Number, System Fault Status, AC Fault Status, FAI Status, FAI Latch Status, FPO Output
Voltage, Battery Voltage, Battery Charge Current, Total Power-up time, Battery Installed time, AC Fault Total, System Fault Total, Battery
State Of Charge, Battery Runtime Test Total, Battery Runtime Test Failed Total, Required Standby, and Actual Standby .
M8 parameters are set on the M8's configure page (NL4 only - see the M8 Manual for more information) .
After setting the devices and parameters to be reported, be sure to click the "Submit" button for each device .