FlexPower Generation 2 DC Power System Installation Manual
14
15
Tamper Switch / User Certificate
Appendix 1 – Tamper Switch Wiring
All FlexPower DC systems with an enclosure include a normally
closed tamper switch for monitoring by the host panel . The
tamper switch can either be brought into a dedicated input in
the panel (see the panel's instructions), to the Event 1 input of a
Netlink Network Module (See the Netlink's Instruction Manual),
or the tamper switch may be series connected into the System
Fault relay in the FPO supply as shown in the illustration .
Any UL1076 installation must use the tamper switch to indicate
the opening or removal of the front door of the enclosure .
Below is a certificate required for UL603 installations, to be cut out, framed and hung adjacent to the FlexPower
Power Supply system after installation . It contains the required battery information, as specified in UL603 .
Specifications for the following model numbers:
FPO150 / FPO250
Maximum Charging Current:
2A
Maximum Battery Capacity:
80AH
Battery Type:
Sealed Lead Acid or Gel Cell
Specifications for the following model numbers:
FPO75
Maximum Charging Current:
1A
Maximum Battery Capacity:
40AH
Battery Type:
Sealed Lead Acid or Gel Cell